background image

Series QV Quick-View

®

 Rotary Position Indicator/Switch

Specifications - Installation and Operating Instructions

Bulletin  F-87

Proximity 

Series QV Quick-View

®

 Rotary Position Indicator/Switch

 is produced 

with up to four individual mechanical or proximity switches. Instructions below include  

installation, as well as adjustment procedures for direct drive and lever drive models.

INSTALLATION

1.  Mounting kits, when provided include couplers, lever arms and screws for 

    mounting the position indicator to a valve or actuator. A position indicator is 

    mounted using direct drive hardware for quarter turn applications (rotational) and 

    lever drive hardware for converting linear motion to rotary. Tubular spacers are also 

    provided for some installations.

2.  For direct drive models, attach appropriate drive yoke or solid block onto the two 

    pins, using a #6-32 X 1/4˝ screw provided. Do not attempt to fabricate your own 

    yokes since this a special spring-tempered material. For direct drives, with the 

    actuator shaft rotated to its counterclockwise position, spread the driving yoke and 

    slip it down onto the square (or rectangular) shaft of the actuator. Attach bracket 

    with two hex cap screws. Before tightening screws, operate control slowly with 

    a wrench or power, and observe that drive shaft and drive yoke are concentric and 

    perpendicular throughout the complete stroke. Adjust position as required and 

    tighten all mounting screws. Check concentricity and perpendicularity.   

3.  For lever drive models, attach the appropriate driving lever onto the shaft. Do 

    not tighten. Attach switch and bracket to actuator, making sure that the lever is 

    free to rotate over the entire range of the actuator stroke. Attach the driving pin 

    or bolt through the lever arm if slotted, or on the driving side of the lever. (It may 

    be necessary to loosen or remove the bracket mounting to accomplish this 

    connection on some actuators.) Operate the actuator very slowly and observe 

    movement of all pins and levers to be sure there are no interferences. Slide lever 

    up or down on switch shaft to the most desirable position. When all motions are 

    made and clearances are adequate, tighten clamp screw on lever that was left 

    loose above. Now tighten all the mounting screws. Re-check the travel of all levers 

    and pins for proper clearance throughout the complete stroke of the actuator.

4.  Push cover down, then turn it counterclockwise and lift straight up to remove.  

    Remove inner cover window. Remove the indicator drum.

5.  Switches are set at the factory in the counterclockwise position listed below:

      2 Switch Unit 

#1 Open             #2 Closed

      4 Switch Unit 

#1, 3 Open         #2, 4 Closed

    90° rotational travel will reverse all of the above positions.

SPECIFICATIONS

Minimum Rotation Travel - Switches Only: 

5°.

Maximum Rotation Travel - Switches Only:

 360°.

Temperature Limits:

 -40 to 180°F (-40 to 82°C).

Switch Type: 

SPDT.

Electrical SPDT Switch Ratings:

 QV-X1XXXX: 10A @ 125/250 VAC; 0.5A 125 

VDC; 10A @ 24 VDC mech. switch; QV-X2XXXX: 0.1A @ 125 VAC; 0.1A @ 24 

VDC mech. switch; QV-X3XXXX: 2A @ 125 VAC; 2A @ 30 VDC prox. switch; 

QV-X4XXXX: 5-25 VDC namur sensor; QV-X5XXXX: 10-30 VDC inductive sensor;

QV-X6XXXX: 10A 125/250 VAC mech. switch.

Lighting Supply Voltage: 

24-28 VDC.

Enclosure Material:

 Polycarbonate housing and conduit.

Conduit Entrance: 

One 3/4˝ NPT.

Enclosure Rating:

 NEMA 4, 4X. Optional explosion-proof, rated: Class I, Groups A, 

B, C, D; Class II, Groups F & G; Div. 2.

Max. Altitude: 

2000 m (6560 ft).

Agency Approvals:

 CE, CSA, cULus.

DWYER INSTRUMENTS, INC.

P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.

Phone: 219-879-8000
Fax: 219-872-9057

www.dwyer-inst.com
e-mail: [email protected]

6-32 UNC

1/4 DP [6.350]

1/4

[6.350]

1/4

[6.350]

2-3/8

[60.33]

3-1/16

[77.79]

1-1/2

[38.10]

2 MTG HOLES

1/4-20 UNC

7/16 DP [11.11]

CONDUIT ENTRANCE

3/4 NPT

3 [76.20] CLEARANCE REQUIRED FOR COVER REMOVAL

4-15/32

[113.5]

1/2

[12.70]

5/16

[7.938]

1/4 DIA. [6.350]

SHAFT LEVER

DRIVE ONLY

1/8 DIA. PINS (2)

4-3/4

[120.7]

MODEL CHART

Example

QV -2 1 01 0 1

QV-210101

Series

QV

Quick-View

®

 valve position indicator/switch

Number of 

Switches

0

1

2

3

4

None*

One*

Two*

Three*

Four*

Switch Type

0

1

2

3

4

5

6

No switches*

10A mechanical snap switch

1A mechanical gold contacts

2A Proximity reed switch*

5-25 VDC namur sensor

10-30 VDC inductive sensor

10A mechanical snap switch

Driving Style

01

02

03

Direct*

Lever*

Namur*

Lighting 

Option

0

1

None*

24-28 VDC bright white LED’s

Visual

Indication

0

1

2

None

Standard (open closed)*

Upside down (open closed)*

Additional 

Options

EX Class I, Div. II, Groups A, B, C & D; Class 

II, Div. II Groups F & G.

*EX, Explosion-proof option available.

Note: 

The 1st, 2nd, 3rd and 6th codes can not all be zero.

Отзывы: