-5-

5.2 Electric Lock Connection

5.2.1  Door Lock Controlled with Internal Power

connect one lock

connect two locks

     Note:

1.  Electronic lock of Power-on-to-unlock type should be used.
2.  The door lock is limited to 12V, and holding current must be less than 250mA.
3.  The door lock control is not timed from Exit Button(EB).
4.  The 

Unlock Mode

 Parameter of Monitor must be set to 0 (by default).

EB

*

LOCK

BUS

PL

S1+

S2+

S-

LOCK

2

nd

1

ST

2

nd

EB

*

1

ST

Jumper position in 

Connect two locks

1-2

EB

*

LOCK

BUS

PL

S1

+

S2

+

S-

Jumper position in 

Connect one lock

1-2

5.2.2  Door Lock Controlled with Dry Contact

     Note:

1.  The external power supply must be used according to the lock.
2.  The jumper must be taken off before connecting.
3.  Setup the 

Unlock Mode

 of Monitor for different lock types.

 • Power-on-to-unlock type:Unlock Mode=0 (by default)
 • Power-off-to-unlock type:Unlock Mode=1

Содержание PRO591

Страница 1: ...2 Wire Intercom System PRO591 592 User Manual 3529 6 21 6 85 7 352 8 76 5 9 PRO591 PRO592...

Страница 2: ...nection 4 5 2 Electric Lock Connection 5 5 2 1 Door Lock Controlled with Internal Power 5 5 2 2 Door Lock Controlled with Dry Contact 5 5 2 3 How to setup the unlock parameter in Monitor 6 5 3 Multi D...

Страница 3: ...ht View LED Speaker Nameplate Call Button Microphone 90 mm 176 mm 23 mm 2 Terminal Descriptions BUS PL S1 S2 S 1 2 ON 1 2 ON MIC adjustment Lock Control Jumper Doorstation Code DIP Main Connect Port 1...

Страница 4: ...S2 Lock power output to connect 2 locks S Lock power output connect to the power input of locks only when using the camera to power the locks if using the external power supply for the locks the S wi...

Страница 5: ...With Rainy Cover 160 165cm 1 2 1 2 3 4 4 3 Placing Name Label Move the plastic cover away to open the transparent name label cover insert a name paper then put the plastic cover back to the panel nam...

Страница 6: ...ng Camera Angle 5 1 Basic Connection use a screwdriver to loosen the screw and then adjust the angle of the camera then fix the screw 5 System Wiring and Connections AC monitor PRODPS PROPS4 1 2 ON L1...

Страница 7: ...Unlock Mode Parameter of Monitor must be set to 0 by default EB LOCK BUS PL S1 S2 S LOCK 2nd 1ST 2nd EB 1ST Jumper position in Connect two locks 1 2 EB LOCK BUS PL S1 S2 S Jumper position in Connect o...

Страница 8: ...n Code Number 0010 Remove all remote control 0011 Add remote control 8000 Set as master unit 0 8001 Set as slaver unit 1 8002 Set as slaver unit 2 8003 Set as slaver unit 3 8004 Set as guard unit 8005...

Страница 9: ...85 260VAC PRODPS PROS5 monitors 1 2 ON L1 L2 PL S1 S2 S 1 2 ON L1 L2 PL S1 S2 S 1 2 ON L1 L2 PL S1 S2 S 1 2 ON L1 L2 PL S1 S2 S 1 2 ON 1 2 ON 1 2 ON 1 2 ON 1 Camera ID 00 ID 10 ID 01 ID 11 2 Camera 3...

Страница 10: ...asic IN OUT Wiring Mode 5 4 Multi Monitors Connection ID 00 1 2 ON Code 0 DIP 6 off Code 14 DIP 6 off Code 15 DIP 6 on 1 2 3 4 5 6 ON 1 2 3 4 5 6 ON 1 2 3 4 5 6 ON monitor monitor monitor 85 260AC PRO...

Страница 11: ...D IN OUT 352 C 4 A B C D IN OUT 85 260AC PRODPS PROS5 1 2 3 4 5 6 ON 1 2 3 4 5 6 ON 1 2 3 4 5 6 ON 1 2 3 4 5 6 ON Code 15 DIP 6 on Code 13 DIP 6 on Code 3 DIP 6 on Code 1 DIP 6 on 1 2 3 4 5 6 ON 1 2...

Страница 12: ...Door Station ID 2 01 set to the third Door Station ID 3 11 set to the fourth Door Station 1 2 ON 1 2 ON 1 2 ON 1 2 ON There are 6 bit switches in total The DIP switches are used to configure the User...

Страница 13: ...1 2 3 4 5 6 ON Code 31 Code 10 Code 21 Note Monitors response button A must set the user code from 0 to 15 and button B set the user code from 16 to 31 A B A Bit 1 to Bit 5 are used to User Code sett...

Страница 14: ...0Vac input 24Vdc 3A output 10 DIN modules Connect with multi doorstations or multi monitors up to 2 or above 3526 24V Power supply 85 260Vac input 24Vdc 1A output for basic kit only 4 DIN modules Conn...

Страница 15: ...DFK When Monitor quantity 20 Cable Usage A B C Twisted cable 2x0 75 mm2 60 60 30 Twisted cable 2x1 mm2 80 80 40 When Monitor quantity 20 Cable Usage A B C Twisted cable 2x1 mm2 70 30 20 Twisted cable...

Страница 16: ...The design and specifications can be changed without notice to the user Right to interpret and copyright of this manual are preserved...

Отзывы: