8.3 Settings - Common
Detector function settings can be found on the website on tab
Config/Detector
. Here are two or four
subtabs found,
Common
,
Detector 1
,
Detector
2
,
Detector 3
etc
.
Figure 10.
Settings for the
Detector
functions.
Settings
–
Auto acknowledge
Parameter
Description
Range
Factory value
Unit
Enable
Activation of automatic acknowledge.
Yes or No
Yes
-
Auto ack delay
Time for automatic acknowledge after fault
detection.
0..48
4
hour
1
The function for transient fault recordings is described in detail in chapter 10. There are limitations in the
number of transient fault recordings that can be stored in runtime memory. If there is a need to ensure
that there is always space for a new disturbance recording, the parameter
Enable immediate ack
can be
checked. Observe that previous recordings can be deleted if the detector restarts due to new events.
Inställningar
–
TFR functions
Parameter
Description
Range
Factory value
Unit
Enable immediate ack
Activation of automatic acknowledge of TFR.
Yes or No
Nej
-
Pretrigger
Time for the first data point of the record.
1..1 000
140
ms
Specialist settings
Parameter
Description
Range
Factory value
Unit
Post Trip Blocking
Time
Time for blocking of detector functions after
fault detection
0..1 000 000
2 000
ms
Test qualifier
Parameter for test
0..4294967295 0
-
1
The unit can be seconds, minutes, or hours. Maximum time is 48 h.