AC POWER SUPPLY 

 
Connect the primary of a 16VAC, 50/60Hz, 40VA 
Transformer to the electrical circuit and run the 
secondary to the AC input on the controller terminals. 

 

CABINET TAMPER SWITCH 
 

The tamper input 
switch should be 
connected to the 
tamper connection 
terminals as shown in 
the diagram below. The 
tamper input opens and 
closes trouble zone 
CPxxx:01 on the 
controller. 

 

 
 
BACKUP BATTERY 

 
It is recommended that a minimum of a 4Ah battery is 
used as the main backup battery. From the accessory 
bag provided, connect the RED and BLACK battery 
termination wires to the B+ and B- terminals.  
 

 

ENCRYPTED MODULE NETWORK 

 
The Protégé System Controller incorporates encrypted RS-
485 communications technology. The isolated 
communications interface offers full galvanic isolation to 
prevent ground loop noise and cross phase ground 
differential between network devices.  

 

 

 
Connection of the communications should be performed 
according to the diagram shown above. It is important that 
the N+ Network Communications Power be supplied from 
an independent battery backed power supply unit or a 
networked module capable of supplying the required power 
to all devices on the RS485 network. 
 
Always connect the Controller’s NA and NB terminals to the 
NA and NB terminals of the communication network. The 
N+ and N- must go to a 12V power supply source as shown 
in the following diagram and connected at ONLY one +12V 
power source. 
 

The EOL (End Of Line) jumper setting MUST 
be set in the ON position for the FIRST and 
LAST module on the RS485 network. EOL is 
ON when the jumper is closest to the EOL 
text.  

 

 
The Network BIAS configuration jumpers allow the 
communication network to be biased using a high or Low 
(Default) resistance.  Set the jumper into the low position 
for normal operation. 

 

 

 
ETHERNET INTERFACE 

 
The communication between the Protégé SMGT System 
Management Suite and the Protégé System Controller 
uses a 10/100 Ethernet network operating the TCP/IP 
protocol. The IP address of the controller can be 
configured using the LCD Keypad Terminal. The default IP 
address is set to a static IP address of 192.168.1.2 with a 
subnet mask of 255.255.255.0. These IP address settings 
are commonly used for internal networks. 
 
When installing an Ethernet connection the Protégé 
System controller should be connected to a suitable 
Ethernet hub or switch.  
 

 

 
Temporary direct connections can be used for onsite 
programming by using a standard Ethernet crossover 
cable. 
 

 