Protec ProPoint PLUS Скачать руководство пользователя страница 10

 

N 93-602-00 Issue 1 

Page 10 of 10 

                © Protec Fire Detection PLC 2015 

6.0  Technical Specifications 

Table 2 Technical Specifications 

Parameter 

Operating Conditions / Limitations 

Power Supply 

21V

DC

 to 28V

DC

, Minimum 2A

DC

: Approved to EN54 Part 4 

Power Supply Fuse 

1.6A  

Voltage Operating Range 

21V

DC

 to 28 V

DC 

Maximum Current 
Consumption 

600mA

DC

 maximum at 24V

DC

 (blower set to 100%, 4 Pipe Detector) 

Loop Protocol 

Protec Algo-

tec™ 6000 

Loop Isolator 

On board consult Protec DEL2110 for details 

Loop Quiescent Current 
Consumption 

0.7mA 

Fault Contact 

Rated at 30 V

DC

 DC 1 A

DC

 maximum [Normally open] 

Input Contacts [1 to 3] 

3 Programmable monitored inputs 30 V

DC 

[Active Low] 

Max applied voltage 30 V

DC

, Open Circuit Voltage ~16 V

DC 

Closed Circuit Resistance 1k5

Ω 

Output Contacts [1 to 5] 

5 Programmable Clean Contact Outputs 
Rated at 30 V

DC

, 1 A

DC

 max [Normally open] 

Power Supply Input 
Monitor 

Normal 24V

DC

 Input, Fault 

≤ 2.5V

DC 

Temperature Range 

0°C to 45°C ambient 

Humidity Limit 

0 - 95% non-condensing ambient 

Indicators 

Power   

[Green LED] 

Fault 

 

[Amber LED] 

Pre-Alarm  

[Amber LED] 

Alarm/Fire  

[Red LED] 

OLED Display 

– Unit status (Faults, Pre-Alarm and Fire), and Commissioning 

menu 

Sensitivity 

A = High

   

 

B = Enhanced

 

 

C = Normal

 

 

 

Number = sampling hole 
alternative to point type smoke 
detector

 

 

Holes 

per 

pipe 

(max) 

Pre-Alarm 

Level

1*

 

Fire Level

1*

 

A1, A2, A3 

150 

 2.2%/m 

200 

 2.9%/m 

B1, B2

 

, B3, B4, B5 

150 

 2.2%/m 

250 

≙ 

3.6

%/m 

C1, C2

 

, C3

 

, C4, C5, C6, C7, C8 

150 

 2.2%/m 

250 

≙ 

3.6

%/m 

Prison 

 

Max area coverage per 
pipe 

800m

2

 (C8 setting to British Standards or see local design -codes) 

CO area coverage 

100m

2

 (Settings A1, B1, C1 and Prison sensitivity only) 

Sensitivity Range 

0.12%/m to 11%/m    

Sound Pressure Levels 

70dB [peak] (Blower at 100%) 

Airflow Monitoring 

High and Low airflow monitoring

 

Airflow Monitoring Range 

± 5% to 50% respectively. For EN54 Part 20 compliance, Unit tolerance set 
to ≤ 20% set by the PC commission tool. 

Airflow Velocity Range 

0.5 m/s to 6 m/s 

Event Log 

256 events stored on FIFO basis 

Environmental History 

Typically 1 Month depending on activity 

IP Rating 

IP30 

Cable Access 

10x 20mm replaceable knockouts 

Cable Termination 

Screw terminal blocks 
(0.2 - 2.5 mm

2

, 30 - 12AWG) 

Connectivity 

TCP/IP Networking Protocol RJ45 Socket connection 
USB type B Socket connection 

Pipe OD 

 

25mm 

Pipe Length Maximum 

200m (To be confirmed by sampling pipe calculation program) 

 
 

Содержание ProPoint PLUS

Страница 1: ...Protec Fire Detection plc Protec House Churchill Way Nelson Lancashire BB9 6RT ENGLAND 44 0 1282 717171 www protec co uk sales protec co uk PROPOINT PLUS ASPIRATING SMOKE DETECTION SYSTEM USER MANUAL ...

Страница 2: ...N 93 602 00 Issue 1 Page 2 of 10 Protec Fire Detection PLC 2015 Document Revision Details Issue Modification Detail Author Date 01 Document Creation RB 15 11 2015 ...

Страница 3: ...This equipment has been manufactured in conformance with the requirements of all applicable EU council directives and regulations Electrical or electronic devices that are no longer serviceable must be collected separately and sent for environmentally compatible recycling in accordance with the European Waste Electrical and Electronic Equipment Directive To dispose of old electrical or electronic ...

Страница 4: ...plications ProPointPlus provides up to four separate detectors within a common aspirator enclosure and therefore provides four individually identifiable areas of detection per aspirator Each of the four plug in Scatter Camber Detectors SCD s detector use independent and integrated alarm decision making Complex algorithms are used to extend the range of particle detection confirm genuine alarms and...

Страница 5: ...is in Fault Pre alarm or Fire providing the buzzer is enabled at commissioning The buzzer can be muted by pressing any button LED indicators are programmed to illuminate corresponding to a specific event The button functions are to navigate thought the commissioning menu and are therefore not a requirement for the user 4 1 Display Figure 4 1 ProPointPlus display detector normal Power LED Green Fir...

Страница 6: ... in the centre of the display When more than one faults is reported the faults are automatically scrolled though each fault on the display The fault LED will be illuminated If the fault is pipe specific the pipe number is displayed in brackets next to the fault for example below shows 1 Airflow Fault describes an airflow fault on pipe 1 Figure 4 2 ProPointPlus displaying a fault condition Refer to...

Страница 7: ...ipe 1 and Pipe 2 are in Pre Alarm condition Warning Pipe 3 and Pipe 4 are in Normal condition The Pre Alarm LED is illuminated any commissioned outputs will activate and the fire condition is reported to the Protec Fire panel Figure 4 3 ProPointPlus displaying Pre Alarm condition The appointed Responsible Person should investigate the relevant area following the official procedures for the buildin...

Страница 8: ...presented as Fire The example picture below shows 4 pipes where Pipe 2 are in Fire condition Pipe 1 Pipe 3 and Pipe 4 are in Normal condition The Fire LED is illuminated any commissioned outputs will activate and the fire condition is reported to the Protec Fire panel Figure 4 4 ProPointPlus displaying Fire Alarm condition The building fire plan must be executed immediately Muting the buzzer The b...

Страница 9: ...r a Protec distributor Link Fault The data RS485 path has failed Contact a Protec operative or a Protec distributor Output Override The inputs check to test option is active activated using the ProView exe PC software Contact a Protec operative or a Protec distributor Corrupt Settings Internal settings are outside the expected values Unit will default to factory settings Contact a Protec operative...

Страница 10: ... LED Alarm Fire Red LED OLED Display Unit status Faults Pre Alarm and Fire and Commissioning menu Sensitivity A High B Enhanced C Normal Number sampling hole alternative to point type smoke detector Holes per pipe max Pre Alarm Level1 Fire Level1 A1 A2 A3 3 150 2 2 m 200 2 9 m B1 B2 B3 B4 B5 5 150 2 2 m 250 3 6 m C1 C2 C3 C4 C5 C6 C7 C8 8 150 2 2 m 250 3 6 m Prison 1 Max area coverage per pipe 800...

Отзывы: