background image

                       

 

DEL2093 Issue 4 02/11  SB   

 

                Page 1 of 3 

 

              Copyright © Protec Fire Detection plc 201 0

 

    

6000

PLUS

/OP/S Installation, Commissioning and Service Instructions

 

Overview 

The Protec 6000

PLUS

/OP/S is a loop powered fire sensor, which reports smoke in its installed location to the fire alarm control 

panel. The sensor is also equipped with an integrated loop powered programmable electronic sounder and an integrated loop 
isolator. 

 

Technical Specification

    

 

Loop protocol 

Protec Algo-tec™ 6000

PLUS

 

Loop isolator fitted 

Yes 

Loop voltage range 

18 to 27V Algo-tec™  loop 

Loop average quiescent current (24V loop) 

0.4mA 

Loop average alarm current ( 24V loop ) 

5mA 

Analogue values 

Smoke 
Normal 40 to 60 bits 
Fault Low <35 bits 
Fault low High>90 bits 

Indications 

On-board red indicating LED  

Environmental operational limits 

-10 to 50 degrees C ( 95% RH no condensation or icing ) 

Sounder Frequencies 

Continuous 990Hz, Warble 730Hz to 990Hz, Pip 990Hz 

Sounder synchronisation 

Sounder synchronisation is achieved by panel control 

IP rating 

IP21C 

Isolator Specification 

Please see Protec DEL2110 for details  

 

Installation

 

1.  Base options: 6000PLUS/BASE  

 

 

LPCB Approved as part of product approval 

6000PLUS/FFBASE 

 

 

LPCB Approved as part of product approval 

28-075-01 (Plug and Play Fast Fix)   

LPCB Approved as part of product approval 

28-075-02 (Plug and Play Surface)   

LPCB Approved as part of product approval 

 

Note: See individual information sheets for base wiring details.

 

 

2.  Install the detector in the base, turn firmly clockwise. 

 

Commissioning 

1.  Each  6000

PLU

S  detector  has  a  unique  serial  number  which  will  be  used  as  part  of  the  commissioning  of  the  fire  alarm 

system.  It  is  necessary  to  remove  one  of  the  ‘peelable  ’  bar  code  labels  present  on  the  product  and  place  it  in  the 
commissioning booklet supplied with each Protec addressable control panel.  The bar code sticker should be placed at the 
relevant loop and address position intended. It is important that serial numbers are not mixed otherwise the addressing of 
the 6000

PLUS

/OP/S will be incorrect when commissioned. 

 
2.  Commission the device onto the system as detailed in the installation and commissioning manual for the fire alarm panel 

being used.  

 

6000

PLUS

/OP/S Certification Details 

EN Standards Compliance/ Approvals table 

 

 
 

 

0 8 3 2 

Protec Fire Detection plc, Nelson, Lancashire, England, BB9 6RT 

10 

0832-CPD-1185

 

EN 54 - 3: 2001 + A1 + A2 

Alarm devices - Sounder 

Type A: For indoor use 

6000PLUS/OP/S 

EN 54 - 7 

Point type smoke detector 

 

6000PLUS/OP/S 

EN 54 - 17: 2005 

Short-circuit isolator 

 

6000PLUS/OP/S 

Technical Data included in this datasheet DEL2093 Issue 4 

 

High sensitivity 

Medium Sensitivity 

Low Sensitivity 

Not approved. 

EN 54 - 7: 2000 + A1: 2002 + A2: 2006 