6000
PLUS
/HT Installation, Commissioning and Service Instructions
Overview
The Protec 6000
PLUS
/HT is a loop powered fire sensor which reports back thermal levels in its installed location to the fire
alarm control panel.
Technical Specification
Loop protocol
Protec Algo-tec™ 6000
PLUS
Loop isolator fitted
No
Loop voltage range
18 to 27V Algo-tec™ Protocol
Loop quiescent current (24V average loop)
0
.
2 mA
Loop alarm current ( maximum )
2.0mA
Analogue values
Thermal
Normal 80 to 180 bits
Fault Low <25 bits
Fault High>250 bits
Indications
On-board red indicating LED
Environmental operational limits
-10 to 50 degrees C ( 95% RH no condensation or icing )
Installation
1. Base options: 6000PLUS/BASE
LPCB Approved as part of product approval
6000PLUS/FFBASE
LPCB Approved as part of product approval
28-075-01 (Plug and Play Fast Fix)
LPCB Approved as part of product approval
28-075-02 (Plug and Play Surface)
LPCB Approved as part of product approval
Note See individual information sheets for base wiring details.
2. Install the detector in the base, turn firmly clockwise.
Commissioning
1. Each 6000
PLUS
detector
has a unique serial number which will be used as part of the commissioning of the fire alarm
system. It is necessary to remove one of the ‘peelable ’ bar code labels present on the product and place it in the
commissioning booklet supplied with each Protec addressable control panel. The bar code sticker should be placed at the
relevant loop and address position intended. It is important that serial numbers are not mixed otherwise the addressing of
the 6000
PLUS
/HT will be incorrect when commissioned.
2. Commission the device onto the system as detailed in the installation and commissioning manual for the fire alarm panel
being used.
6000
PLUS
/HT Certification Details
EN/CEA Standards Compliance/ Approvals table
0 8 3 2
Protec Fire Detection plc, Nelson, Lancs
10
0832-CPD-1169
EN 54 - 5:
Point type Heat Detector
Class A1/A2
6000
PLUS
/HT
Technical Data included in this datasheet. DEL 2088 Issue 4
High Sensitivity
Medium Sensitivity
Low Sensitivity
EN 54-5: 2000 + A1: 2002 Class A1
EN 54-5: 2000 + A1: 2002 Class A2
Not approved.
Equivalent to EN 54-5: 2000 + A1: 2002
Class B