6000

PLUS

/HT Installation, Commissioning and Service Instructions

 

Overview

 

The  Protec  6000

PLUS

/HT  is  a  loop  powered  fire  sensor  which  reports  back  thermal  levels  in  its  installed  location  to  the  fire 

alarm control panel.  

 

Technical Specification

    

 

Loop protocol 

Protec Algo-tec™ 6000

PLUS

 

Loop isolator fitted 

No 

Loop voltage range 

18 to 27V Algo-tec™ Protocol 

Loop quiescent current (24V average loop) 

0

.

2 mA 

Loop alarm current ( maximum ) 

2.0mA 

Analogue values 

Thermal 
Normal 80 to 180 bits 
Fault Low <25 bits 
Fault  High>250 bits 

Indications 

On-board red indicating LED  

Environmental operational limits 

-10 to 50 degrees C ( 95% RH no condensation or icing ) 

 

Installation

 

1.  Base options:  6000PLUS/BASE  

 

 

LPCB Approved as part of product approval 

 

 

6000PLUS/FFBASE 

 

 

LPCB Approved as part of product approval 

 

 

28-075-01 (Plug and Play Fast Fix)   

LPCB Approved as part of product approval 

 

 

28-075-02 (Plug and Play Surface)   

LPCB Approved as part of product approval 

 
Note See individual information sheets for base wiring details. 

 

2.   Install the detector in the base, turn firmly clockwise. 

 

 

Commissioning 

1.  Each  6000

PLUS 

detector

 

has  a  unique  serial  number  which  will  be  used  as  part  of  the  commissioning  of  the  fire  alarm 

system.  It  is  necessary  to  remove  one  of  the  ‘peelable  ’  bar  code  labels  present  on  the  product  and  place  it  in  the 
commissioning booklet supplied with each Protec addressable control panel.  The bar code sticker should be placed at the 
relevant loop and address position intended. It is important that serial numbers are not mixed otherwise the addressing of 
the 6000

PLUS

/HT will be incorrect when commissioned. 

 
2.  Commission  the device  onto  the  system as detailed  in  the installation and commissioning  manual for  the  fire  alarm panel 

being used.  

 

6000

PLUS

/HT Certification Details 

 

EN/CEA Standards Compliance/ Approvals table 

 

 
 

 

0 8 3 2 

Protec Fire Detection plc, Nelson, Lancs 

10 

0832-CPD-1169 

EN 54 - 5: 

Point type Heat Detector 

Class A1/A2 

6000

PLUS

/HT 

Technical Data included in this datasheet. DEL 2088 Issue 4 

 

High Sensitivity 

Medium Sensitivity 

Low Sensitivity 

EN 54-5: 2000 + A1: 2002 Class A1 

EN 54-5: 2000 + A1: 2002 Class A2 

Not approved.  
Equivalent to EN 54-5: 2000 + A1: 2002 
Class B 