Prostat SureTest PGT-61-164 Скачать руководство пользователя страница 5

 

 

PGT-61-164 SureTest Circuit Analyzer

 

4

 

 

 

 

SureTest Circuit Analyzer 

1. Menu 

Structure 

2. Navigation 

Buttons 

3. 

GFCI Test Button 

4. 

AFCI Test Button (Not 

included on the 61-164) 

 
 
 
 

III. Menu 

Navigation 

 

The microprocessor’s top priorities are to take live measurements and then analyze the 
data. Hence, the microchip occasionally will not recognize the keypad buttons being 
rapidly depressed, while it’s executing these changes. 
 
The measurements taken by the SureTest Model 61-164 are broken into five main menus 
positioned down the left side of the display: Wiring Configuration (

 

 

), Voltage (

V

), 

Voltage Drop ( 

V

D

 ), ASCC, and Impedance ( 

Z

 ). To navigate to each of the main menus, 

use the down arrow button (

). 

 
The Wiring Configuration (

 

 

) screen indicates correct wiring, reverse polarity, 

hot/ground reversal and no ground conditions by sequencing the three balls. The label on 
the back of the product explains the wiring sequence indications. 
 
The Voltage ( 

) menu displays the True RMS line voltage in real-time. This main menu 

has a sub-menu positioned horizontally at the bottom of the screen that displays the line 
voltage (

RMS HN

), ground-to-ground voltage (

RMS GN

), Peak Voltage (

PEAK

), and 

Frequency ( 

H

Z

 ). To navigate through the submenu, use the side arrow button (

). 

 
The Voltage Drop ( 

V

D

 ) screen dual displays percent voltage drop with a 15 amp load 

along with the resultant loaded voltage ( 

V

L

 ). This main menu has a submenu, which also 

displays the percent voltage drop and loaded voltage with 20 amp and 12 loads. To 
navigate through the submenu, use the side arrow button ( 

 ). 

 
The 

ASCC

 screen displays the 

A

vailable 

S

hort-

C

ircuit 

C

urrent that the branch circuit can 

deliver through the breaker during a bolted fault (dead-short) condition. 
 
The Impedance (

Z

) main menu displays the impedance in ohms (

Ω

) of the hot conductor. 

This main menu has a sub-menu positioned horizontally at the bottom of the screen that 
also displays the neutral (

N

) and ground (

G

) conductor impedances. To navigate through 

the submenu, use the side arrow button ( 

 ). Note that testing the ground impedance will 

trip a GFCI protected circuit.  
 
 
 
 
 

Содержание SureTest PGT-61-164

Страница 1: ...P R O F E S S I O N A L S T A T I C C O N T R O L P R O D U C T S Operations Manual SureTest Universal Circuit Analyzer PGT 61 164 SureTest Manufactured by Ideal Industries Sycamore Illinois USA...

Страница 2: ...n the United States of America No part of this manual may be used or reproduced in any manner whatsoever without written permission For information contact PROSTAT Corporation 1072 Tower Lane Bensenvi...

Страница 3: ...lyzer 2 TABLE OF CONTENTS PROSTAT PGT 61 164 SURETEST CIRCUIT ANALYZER Title Page I Introduction 3 II General Operation 3 III Menu Navigation 4 IV GFCI Test Button 5 V Testing Procedure 5 VI GFCI Test...

Страница 4: ...Frequency Measures Hot Neutral and Ground conductor impedances Identifies proper wiring in 3 wire receptacles Identifies false bootleg grounds Tests GFCI s for proper operation Includes 1 ft extension...

Страница 5: ...nu displays the True RMS line voltage in real time This main menu has a sub menu positioned horizontally at the bottom of the screen that displays the line voltage RMS HN ground to ground voltage RMS...

Страница 6: ...lse Ground If the wiring condition is other than normal the SureTest is limited on its measurements that can be performed If a no ground condition exists only the line voltage and voltage drop measure...

Страница 7: ...ute loads on the circuit High Resistance connection within the circuit or at the panel Locate high resistance connection device and repair replace Line Voltage 120 VAC 220 VAC 108 132 VAC 198 242 VAC...

Страница 8: ...e run or too much current on the circuit Check the wire to ensure that it is sized per sode and measure the current on the branch circuit If a voltage drop reading changes significantly from one recep...

Страница 9: ...ood ground to adequately protect equipment from transient overvoltages Note that a small amount of current is applied to the ground conductor to accurately measure its impedance By the inherent nature...

Страница 10: ...test a GFCI in a 2 wire system no ground the 61 175 ground continuity adapter sold separately must be used Connect the alligator clip on the adapter to a ground source such as to a metal water or gas...

Страница 11: ...ime GFCI maybe installed improperly Check wiring for proper installation in accordance with manufacturer s instructions and NEC GFCI Test GFCI trips within trip time GFCI doesn t trip GFCI may be defe...

Страница 12: ...Instrument has been evaluated and complies with insulation category III Overvoltage category III Pollution degree 2 in accordance with IEC 644 Indoor use Measurement Specifications All specifications...

Страница 13: ......

Страница 14: ......

Страница 15: ......

Страница 16: ...Copyright 2001 2007 Prostat Corporation Printed in U S A 1072 Tower Lane Bensenville IL 60106 USA www prostatcorp com...

Отзывы: