PGT-61-154 SureTestCircuit Analyzer
10
ground-neutral voltage may result in inconsistent or intermittent equipment
performance. Pressing the down arrow button (
↓
) moves the unit to the next
menu selection – Line Impedance.
Troubleshooting Tips
Measurement Expected
Result
Problem Possible
Causes
Possible
Solutions
Ground-Neutral
Voltage
< 2V
High G-N voltage
•
Current
leading from
neutral to
ground
•
Unbalanced
3-phase
system
•
Harmonic
content
returning on
neutral in 3-
phase
system
•
Identify
source of
leakage
(multiple
bonding
points)
•
Check load
balance and
re-distribute
load
•
Oversize
neutral or de-
rate
transformer
to dissipate
heat