ILX56-PBS
Setup
ControlLogix® Platform
User Manual
Page 24 of 87
DPV1 Alarms
The DPV1 Alarms configuration is shown in the following figure. The slave device DPV1
Alarms configuration window is opened by either double-clicking on the slave device in the
tree, or right-clicking the slave device and selecting
Configuration
.
NOTE:
The Size of the DPV1 Alarm
must
be greater than 4 or the alarm
triggering will not execute.
Figure 3.15
– Device DPV1 Alarms configuration parameters (Logix)
The DPV1 configuration consists of the following parameters:
Parameter
Description
Size
The size (bytes) of the Alarm object.
Tagname
The Logix Tagname from where the alarm data will be read. (Logix
Only)
Table 3.9
– Device DPV1 Alarms configuration parameters
NOTE:
The PROFIBUS DP Master connected to the ILX56-PBS will be able to
configure the following alarms;
Diagnostic Alarm
Process Alarm
Pull Plug Alarm
Status Alarm
Update Alarm
Manufacturer Specific Alarm