![ProSoft Technology ProLinx PDPM Скачать руководство пользователя страница 11](http://html1.mh-extra.com/html/prosoft-technology/prolinx-pdpm/prolinx-pdpm_protocol-manual_1618989011.webp)
PDPM ♦ ProLinx Gateway
Functional Overview
PROFIBUS DP Master
Protocol Manual
ProSoft Technology, Inc.
Page 11 of 70
June 24, 2013
In addition to data from the master port, status and error information generated
by the module can also be mapped into the internal database.
2.6
Master/Slave Communication Phases
The communication between the Master and the slaves takes place in the
following phases:
Parameterization and configuration phase
Usable data transfer phase
Before a DP slave can be integrated into the usable data transfer phase, the
parameterization and configuration phase runs a device identification test that
verifies that the planned configuration matches the actual device configuration for
each slave in the PROFIBUS network. The test verifies that:
The device is actually there
It is the right type of device
The station address set on the device matches the station address in the bus
configuration
The formats, telegram length information, and bus parameters are correct
and
The number of configured inputs and outputs is correct
2.7
Port Physical and Protocol Specifications
The ProLinx module supports the PROFIBUS Master protocol as a Master on
either a Mono-Master or Multi-Master network.
ACTIVE
ERR
Port 0
ACTIVE
ERR
Debug
ACTIVE
ERR
Port 0
Config
TKN
ERR
RUN
RDY
Profibus Master