Reference ProLinx
DNPS
♦
ProLinx Gateway
User Manual
DNP 3.0 Slave
ProSoft Technology, Inc.
Page 41 of 86
December 1, 2009
3 Reference
In This Chapter
Product Specifications ........................................................................... 41
Communication Port Cables.................................................................. 44
Functional Overview.............................................................................. 50
DNP Collision Avoidance....................................................................... 64
IIN Response: Slave Port ...................................................................... 65
IIN Bit Definitions ................................................................................... 66
Event Size Computation ........................................................................ 67
Device Profile ........................................................................................ 68
Subset Definition ................................................................................... 70
3.1 Product
Specifications
3.1.1 DNP 3.0 Slave Port Specifications
Type Specifications
General Parameters
Internal Database
Binary Inputs:
0 to 100 word count
Analog Inputs:
0 to 100 points of analog input data
Float Inputs: 250 points
Double Inputs: 125 points
Counters:
0 to 50 points of counter data
Binary Outputs: 0 to 100 word count
Analog Outputs: 0 to 100 points of analog output
Float Outputs: 250 points
Double Outputs: 125 points
Binary Input Events: 0 to 100 binary input event buffer
Analog Input Events: 0 to 100 analog input event buffer
Communication parameters
Port 0: Baud Rate: 110 to 38.4K baud
Stop Bits: 1
Data Size: 8 bits
Parity: None
RTS Timing delays: 0 to 65535 milliseconds
DNP Mode
DNP 3.0 Slave - Level 2
DNP Object Support
See Reference chapter for full Object Definition document
Содержание ProLinx DNPS
Страница 1: ...ProLinx DNPS ProLinx Gateway DNP 3 0 Slave December 01 2009 USER MANUAL...
Страница 4: ......