PLX3x Series ♦ Multi-Protocol Gateways
EIP Protocol
User Manual
ProSoft Technology, Inc.
Page 73 of 215
January 25, 2018
5.3.3 EIP Error Codes
The gateway stores error codes returned from the command list process in the
command list error memory region. A word is allocated for each command in the
memory area. The error codes are formatted in the word as follows: The least-
significant byte of the word contains the extended status code and the most-
significant byte contains the status code.
Use the error codes returned for each command in the list to determine the
success or failure of the command. If the command fails, use the error code to
determine the cause of failure.
Warning: The gateway-specific error codes (not EtherNet/IP/PCCC compliant) are returned from
the gateway and never returned from an attached EtherNet/IP/PCCC slave device. These are error
codes that are part of the EtherNet/IP/PCCC protocol or are extended codes unique to the PLX3x
gateway. The most common errors for the EtherNet/IP/PCCC protocol are shown below.
Local STS Error Codes
Code (Int)
Code (Hex) Description
0
0x0000
Success, no error
256
0x0100
DST node is out of buffer space
512
0x0200
Cannot guarantee delivery (Link Layer)
768
0x0300
Duplicate token holder detected
1024
0x0400
Local port is disconnected
1280
0x0500
Application layer timed out waiting for response
1536
0x0600
Duplicate node detected
1792
0x0700
Station is offline
2048
0x0800
Hardware fault
Remote STS Error Codes
Code (Int)
Code (Hex) Description
0
0x0000
Success, no error
4096
0x1000
Illegal command or format
8192
0x2000
Host has a problem and will not communicate
12288
0x3000
Remote node host is missing, disconnected or shut down
16384
0x4000
Host could not complete function due to hardware fault
20480
0x5000
Addressing problem or memory protect rungs
24576
0x6000
Function not allowed due to command protection selection
26872
0x7000
Processor is in Program mode
-32768
0x8000
Compatibility mode file missing or communication zone problem
-28672
0x9000
Remote node cannot buffer command
-24576
0xA000
Wait ACK (1775-KA buffer full)
-20480
0xB000
Remote node problem due to download
Содержание PLX3x Series
Страница 1: ...PLX3x Series Multi Protocol Gateways January 25 2018 USER MANUAL...
Страница 4: ......
Страница 42: ...PLX3x Series Multi Protocol Gateways User Manual Page 42 of 215 ProSoft Technology Inc January 25 2018...
Страница 48: ...PLX3x Series Multi Protocol Gateways User Manual Page 48 of 215 ProSoft Technology Inc January 25 2018...
Страница 94: ...PLX3x Series Multi Protocol Gateways User Manual Page 94 of 215 ProSoft Technology Inc January 25 2018...