ProSoft Technology 3170-PDP Profibus DP Скачать руководство пользователя страница 4

3170-PDP Installation Guide

4

STATUS Indicator

    Indication

Status

 OFF

 No power

 Solid Green

 Normal operation

 Flashing
 Red/OFF

 Recoverable fault

- Flex I/O module defective
- Incorrect Flex I/O

   module installed

- Node address changed since
  power up

 Solid Red

   Unrecoverable fault

            PROFIBUS Indicator

    Indication

Status

  OFF

 No power or no communication

  Solid Green  Data is being transmitted and

  recieved

  Flashing
  Red/OFF

 Recoverable fault

 - Invalid Send Parameter data
 - Invalid Check Configuration data

  Solid Red

 Unrecoverable fault

 - Unable to communicate

3170-PDP Specifications

3170-PDP Flex I/O Profibus

Adapter Specifications

    I/O Capacity

 8 modules

  Input Voltage Rating

  24V dc nominal

  Input Voltage Range

 19.2V to 31.2V dc (includes 5% ac
  ripple)

  Communication Rate

 All rates up to 12Mbit/s

  Indicators

 STATUS LED - red/grn
 PROFIBUS LED - red/grn

  Flexbus Output Current

  640mA maximum @ 5V dc

   Power Consumption

  400mA maximum from external 24V
  dc supply

   Power Dissipation

   7.68W maximum @ 19.2V dc

  Environmental Conditions
  Operational Temperature

 Storage Temperature

0 to 55oC (32 to 131oF)

-40 to 85oC (-40 to 185oF)

  PROFIBUS Connector

    9-pin D-shell

  PROFIBUS Drop Cable

   Standard drop cable

 Power Conductors

Wire Size

Category

12 gauge (4mm2) stranded maximum

  3/64 inch (1.2mm) insulation max.

21

 Agency Certification
(when product or packaging is
 marked)

    

 

•    

CE marked for all applicable

          directives.

PNO

1

 Use this conductor category information for planning conductor routing. Refer to

      publication
      1770-4.1, “Industrial Automation Wiring and Grounding Guidelines."

Set the Node Address

  

Set the node adress using the2-position pen-push switches. Use a
ball-point pen to press either the + or – buttons to change the
number. Valid settings range from 00 to 99

Network
Address
Switches

Note

 The adapter automatically sets the baud rate at power-up.

STATUS Indicator
(gree/red)

PROFIBUS
Indicator
(green/red)

LED Indicators

  