Setting up the pump

2.1  General

Familiarise yourself with the process: We describe here how to set up the

pump for PROFIBUS

®

 mode. You will later meet the pump's

PROFINET

®

 protocol via the DULCOnvert in the master control system.

For this reason, "PROFIBUS

®

" is interchangeable with "PROFINET

®

" at

many points.
You can set up a pump with PROFIBUS

®

 module in the same way as the

standard pump, with the addition of bus functionality.
The pump interrupts the set-up process in the event of a pause longer

than 60 seconds.

2.2  Setting the slave address

The address is pre-set to "125". There is no need to manually set the slave

address if a master in the PROFIBUS

®

 segment assigns the slave

addresses.
1.

Press the   

[Menu]

 key.

2.

Turn the 

[Clickwheel]

 to 

‘Fieldbus’

 and press the 

[Clickwheel]

.

3.

Turn the 

[Clickwheel]

 to 

‘BUS address’

 and press the 

[Clickwheel]

.

INFORMATION!: Always set the 3-digit PROFIBUS

®

 address to "002".

1.

Set the 1st digit with the 

[Clickwheel]

 and press the   

[Priming]

 key.

ð

The 2nd digit of the address is highlighted.

2.

Set the 2nd digit with the 

[Clickwheel]

 and press the   

[Priming]

key.

ð

The 3rd digit of the address is highlighted.

3.

Set the 3rd digit with the 

[Clickwheel]

 and press the 

[Clickwheel]

.

ð

The address has now been fully entered.

2.3  Switching PROFIBUS

®

 to active/inactive

Set the 

‘Fieldbus’

 to 

‘active’

 in the operating menu for the pump to be

controlled by the PROFIBUS

®

.

1.

Press the   

[Menu]

 key.

2.

Turn the 

[Clickwheel]

 to 

‘Bus active’

 and press the 

[Clickwheel]

.

3.

Turn the 

[Clickwheel]

 to 

‘Active’

 or 

‘Inactive’

 and press the

[Clickwheel]

. You’re done!

All external inputs of the pump, such as level monitoring, dosing monitor

and external control (pause, contact input, analogue input), will continue to

function while the PROFIBUS

®

 is 

‘active’

. The external inputs lead to the

expected reactions as is the case with a pump without PROFIBUS

®

module. The pump transmits relevant information via the PROFIBUS

®

 to

the master (PLC, PC etc.).
If the PROFIBUS

®

 is set to 

‘inactive’

, the settings for the operating mode

previously selected will be reloaded.
If the pump is switched to another operating mode, then the pump will stop

and can only be restarted using the 

[Stop/Start]

 key.

Setting up the pump

 

 

 

4

Содержание DULCO flex Control

Страница 1: ...in conjunction with the operating instructions for the pump EN Part no 999564 Version BA DX 042 02 22 EN Please carefully read these operating instructions before use Do not discard The operator shal...

Страница 2: ...ive inactive 4 3 PROFINET settings 5 4 Special features in active PROFIBUS mode 6 4 1 General 6 4 2 Displays 6 4 3 LEDs on the PROFIBUS module 6 5 Assembly and electrical installation 7 6 Operation 8...

Страница 3: ...Simply insert the plug in module into the front of the pump The menu item Fieldbus then appears in the operating menu and the PRO FIBUS symbol appears in the status bar of the display The pump can th...

Страница 4: ...the address is highlighted 2 Set the 2nd digit with the Clickwheel and press the Priming key The 3rd digit of the address is highlighted 3 Set the 3rd digit with the Clickwheel and press the Clickwhe...

Страница 5: ...stal lation chapter 3 Select Update accessible devices in the TIA portal under Online access Fig 1 Update accessible devices The default name is nl51ndpl 4 Assign a new name via Online diagnostics Fig...

Страница 6: ...ed to PROFIBUS mode the pump will stop and can only be restarted using the PROFIBUS 4 2 Displays There are additional identifiers in the operating display when PROFIBUS mode is running Stop PROFIBUS t...

Страница 7: ...ew of the large threaded connector on the left of the housing and remove the rubber insert 3 Correctly thread the clamping screw the right way round onto the PROFINET cable 4 Guide the PROFINET cable...

Страница 8: ...ORMATION The initial parameters must be transmitted from the master so that the pump can engage in cyclic data transmission Only standard parametrisation is needed for this as there are no application...

Страница 9: ...s in priming mode higher level function 10 Auxiliary Pump is in auxiliary mode higher level function 11 Pause Pump has been switched to pause higher level function 12 Module Fieldbus mode active 13 Ho...

Страница 10: ...atch metering is activated in batch operation Batches can also be activated via the contact input Batch memory 13 BYTE If the batch memory is activated and a new batch is triggered during batch meteri...

Страница 11: ...eset Reset revolution counter 24 UINT8 If the value changes from 1 to 0 the revolution counter is reset Volume counter 25 FLOAT32 Volume counter Litres per revolu tion 26 FLOAT32 Litres per revolution...

Страница 12: ...C Degree of protection IP66 with professional installation PROFIBUS cable length 2 m Plug in power unit length 1 5 m Housing HxWxD 140x110x60 mm without threaded connectors Electrical data Degree of p...

Страница 13: ...ipment this device features the symbol showing a waste bin with a line through it The device must not be disposed of along with domestic waste To return the device use the return and collection system...

Страница 14: ...14...

Страница 15: ...15...

Страница 16: ...999564 1 en_GB 2022 ProMinent GmbH Im Schuhmachergewann 5 11 69123 Heidelberg Germany Telephone 49 6221 842 0 Fax 49 6221 842 419 Email info prominent com Internet www prominent com...

Отзывы: