Electrical interface for pin 1 "Pause" - pin 2 "External contact" - pin
5 "Auxiliary frequency"
Data
Value Unit
Voltage with open contacts
5 V
Input resistance
10 kΩ
Max. pulse frequency
25 pulse/s
Min. pulse duration
20 ms
Min. pause between pulses
3 ms
Control via:
n
potential-free contact (load: 0.5 mA at 5 V) or
n
Semiconductor switch (residual voltage < 0.7 V)
Electrical interface for pin 3 "mA input" (with identity code charac‐
teristic "Control version": A - "External Analogue")
Data
Value Unit
Input apparent ohmic resistance,
approx.
120 Ω
Tab. 1: Behaviour of the pump
At approx. 0.1 mA (4.1 mA) the metering pump makes its first
metering stroke.
At approx. 19.9 mA the pump moves to continuous operation at
180 strokes / min .
With current signals above 23 mA, the red fault indicator lights
up, the pump stops and any fault indicating relay fitted switches
(a fault is pending).
Only with 4...20 mA: With current signals below 3.8 mA, the red
fault indicator lights up, the pump stops and any fault indicating
relay fitted switches (Fault for example with a cable break).
Pin
Function
5-wire cable
2-wire cable
1
Pause
brown
bridged at pin
4
2
External con‐
tact
white
brown
3
mA input*
blue
-
4
Earth GND
black
white
5
Auxiliary fre‐
quency
grey
-
* with identity code characteristic "Control version": A - "External
Analogue"
Refer to the functional description for the hierarchy
of functions and operating modes.
1
5
4
2
3
P_BE_0014_SW
Fig. 9: Pump assignment
2
4
5
1
3
P_BE_0015_SW
Fig. 10: Cable assignment
Electrical installation