RG3000-E REFRIGERANT RECOVERY 

ADDITIONAL INFORMATION 

 
To achieve the deepest final vacuum, use the tank cooling method to lower the head 
pressure on the recovery tank. Repeat as necessary to achieve the desired vacuum 
level. 

NOTE:

 If there is no liquid in the recovery tank, then the cooling method will not work. In 

this case, use an empty tank that has been fully evacuated to achieve the final vacuum 
level required.   
 
To maximize recovery rates use the shortest possible length of 3/8” or larger hose. A 
hose no longer than 90cm is recommended.  Always remove all unnecessary hose core 
depressors and Schraeder valves from valve connections (using the proper valve core 
removal tool) for maximum flow.  Deformed rubber seals and core depressors in hoses 
and faulty or unnecessary Schraeder valves can restrict flow by up to 90%. 
 
If the tank pressure exceeds 31,5 bar, use the tank cooling procedure to reduce the 
tank pressure. When recovering large amounts of liquid, use the “PUSH/PULL” method 
of recovery (see diagram below). 
 

CAUTION:

 

When using the “PUSH/PULL” method, you must use a scale to prevent 

overfilling the storage tank. Once the 

“PUSH/PULL” siphon is started, it can continue 

and overfill the storage tank even if the tank is equipped with a float level sensor. The 
siphon can continue even when the machine is turned off. You must manually close the 
valves on the tank and the unit to prevent overfilling the recovery tank. 
 

SET-UP DIAGRAM FOR TANK PRE OR SUB COOLING 

PROCEDURE 

 

 

To  start  you  must  have  a  minimum  of 
2,5 kg of liquid refrigerant in the tank. 
 
Throttle  the  outlet  valve  so  that  the 
outlet  pressure  is  7  bar  (100  psi) 
greater  than  the  inlet  pressure,  but 
never more than 31,5 bar (450 psi). 
 
Run the unit until the tank is cold. 
 

Содержание RG3000-E

Страница 1: ...USER S MANUAL RG3000 E...

Страница 2: ...7 9 C Purging the non condensable gases 10 IV Diagrams A Parts list 11 B Refrigerant flow diagram 12 C Wiring diagram 13 V Automatic safety pressure switch 14 VI Care and maintenance 15 VII Technical...

Страница 3: ...ically driven and controlled Be sure to disconnect the unit from the power source before servicing it 7 Always store refrigerant containers in a cool dry place 8 Always open service and cylinder valve...

Страница 4: ...only approved cylinders with a minimum of 41 bar working pressure that meet the current regulations NOTE Recovery cylinders are designed for different pressures Do not exceed the working pressure of...

Страница 5: ...elieve any high pressure and or tank overfill 4 WARNING Never overfill storage tanks Overfilling may cause tanks to explode 5 A scale must be used to avoid overfilling the storage tank 6 Tanks and fil...

Страница 6: ...n The fan and compressor will start running Slowly open the inlet valve on the unit and the refrigerant will start to move OPERATING PROCEDURES NOTE To change from Recovery mode to Purge If available...

Страница 7: ...n You should hear the fan and compressor running 8 Slowly open the inlet valve on the RG3000 E a If the compressor starts to knock slowly throttle back the inlet valve until the knocking stops b If th...

Страница 8: ...the unit until desired vacuum is achieved 4 Turn the RG3000 E off 5 Close the valves on the recovery tank and the outlet valve on the RG3000 E 6 Disconnect and store all hoses 7 Replace the in line fi...

Страница 9: ...oses and faulty or unnecessary Schraeder valves can restrict flow by up to 90 If the tank pressure exceeds 31 5 bar use the tank cooling procedure to reduce the tank pressure When recovering large amo...

Страница 10: ...COVERY This method is the fastest method for recovering vapor refrigerant SET UP DIAGRAM FOR PUSH PULL METHOD Push pull only works with large systems where the liquid is readily accessible Do not use...

Страница 11: ...000 E 9 OPTIONAL RECOVERY TANK PRE OR SUB COOLING FOR FIXED HOSE SET UP Normal recovery Tank Vapor valve is closed Tank pre or sub cooling Tank Vapor valve is open and both Manifold Gauge Set valves a...

Страница 12: ...rt Find the temperature on the chart and look across to the corresponding pressure for the type of refrigerant in the tank Determine how that relates to the reading on the gauge 5 If the pressure read...

Страница 13: ...1 Manifold Assy High Side 1 110 201201 001 Low Side Gauge only 1 110 201202 001 High Side Gauge only 1 12 145 ATPEL1310 Power Switch 1 13 140 ATPRR121917 Power Receptacle 1 14 111 ATP100419 Fuse Holde...

Страница 14: ...risk of damage to your RG3000 E by preventing foreign material from entering the unit Special consideration for filtration must be given when you know you are servicing a machine that has Burned Out...

Страница 15: ...Advanced Test Products Europe RG3000 E 13 RG3000 E WIRING DIAGRAMM...

Страница 16: ...The following precautions should be taken if the Safety Pressure Switch is activated a Suspected overfilling of the recovery bottle Connect the recovery bottle to another bottle with spare capacity s...

Страница 17: ...uld be labeled and used exclusively for one type of refrigerant only Do not use this unit in the vicinity of spilled or open containers of gasoline or other combustible liquids Avoid the use of extens...

Страница 18: ...R408A R409A R410A R417A R500 R502 R503 R507 R422A R422D R427A R1234YF Not intended for use with Category I e g R11 R123 II e g R114 nor VI e g R13 R23 refrigerants Power Source 230V 50Hz Power 250 W D...

Страница 19: ...be well advised to own at least one tank for every refrigerant type serviced plus an extra for burnouts and other unknowns Planning Ahead Knowing the quantity of refrigerant is important for planning...

Страница 20: ...e isn t economically justified in most cases It s still a great idea to do as much cleaning of refrigerant going back into the same system or owners system as possible We recommend using the largest h...

Страница 21: ...frigerant or when transferring from one tank to another The rate of liquid transfer is very much dependent on hose size with larger hoses providing much better throughput Another trick is to chill the...

Страница 22: ...unit CONNECT UNIT TO 230V 50HZ POWER SUPPLY MOTOR RUNS WHEN POWER SWITCH IS TURNED ON POWER SUPPLY OK CIRCUIT BREAKER TRIPPED UNIT PUMPS INTO HIGH PRESSURE SHUT OFF IS UNIT IN HIGH PRESSURE SHUT OFF...

Отзывы: