REV 7.5.1 / PL-INSTL-TREECOM-EN
VAV Zone controllers with Digital Wall Sensor
The PL-VC2000 or C1050 VAV controllers can be connected to a communicating digital wall sensor (T1000, T500,T200) using a PL-TREE-
COM.
(Figure 9)
1. The PL-TREE-COM connected to the communicating wall sensor NEEDS to be set as the "ROOT". (INT port)
2. The PL-TREE-COM connected to the VAV controller must be set as the "LEAF". (INT port)
3. Both TREE-COM modules must have their dipswitches set for the same channel number.
Figure 9
PL-T1000
PL-TREE-COM
Channel: 1
ROOT
PL-VC2000
Modbus: 1
PL-TREE-COM
Channel: 1
LEAF