Proliphix EPA-20 and EPA-60 Installation Guide, Release 1.0
Part No. 600-01004-000, Rev. 2
Mounting and Wiring the EPA-20 and EPA-60
4
Untwist the wire pairs.
5
Attach the other end of the CAT5, CAT5E, or CAT6 cable to the Proliphix thermostat.
to wire the EPA-20.
to wire the EPA-60.
Figure 1 EPA-20 Wiring
Caution
Do not strip individual wires.
Note
The 110 terminal and RJ-45 ports with the same number are part of the same
connection. The connection is from the thermostat backplate into the EPA then
continues from the RJ-45 to the network (router, switch, etc.).
Caution
You MUST use the T568A wiring scheme on the thermostat backplate when
connecting to the EPA. The EPA 110 block is wired as a T568A terminal, so both
ends of the same wire must use the same scheme.
Note
I
You must verify the appropriate wires are placed in the correct pin holes on the
adapters’s punch down terminal.
Ethernet
Power
Adapter
Model EPA-20
1
2
1
2
24
V
D
C
white-blue
white-orange
white-green
white-brown
blue
orange
green
brown
24VDC
Power Supply
CAT5
wire to
Proliphix
Device
CAT5 Cable to
Router or
Ethernet switch
110 Punch
down Terminal
CAT5 jack