5) Test Function:
Test the function of the UPS system by either pressing the On-Switch “I” or
disconnecting the input of the UPS system from the power supply.
6) Turn Off the UPS:
6.1) In Inverter Mode:
Press “ “ button continuously for more than 1 second to turn off the UPS.
Then the UPS will get into self-test status first. After having finished the
self-test, the UPS will get into bypass mode and the Utility Power LED and
Bypass LED will light up. At this time, the UPS might has output. Disconnect
the utility power
to turn off the output.
6.2) In Battery Mode:
Press “ “ button continuously for more than 1 second to turn off the UPS.
Then the UPS will get into self-test status first. After having finished the
self-test, the UPS will be turned off completely.
7) Audible Alarm Mute Function: If the alarm is too annoying in battery mode, you
may press “I” button continuously for more than 1 second to clear it. Moreover,
the alarm will be enabled when the battery is low to remind you to shutdown the
load soon.
8) Operation Procedure of External Battery for Long Backup time Model (“S” Model)
The units with CE markings—
(1) Use the battery pack with voltage: 36VDC for 1KS (3 pcs of 12V batteries),
96VDC for UPS T2000S/ 3000S (8 pcs of 12V batteries). Connection of
batteries more than or less than required will cause abnormality.
(2) One end of the external battery cord is a plug for connecting the UPS and the
other end has a plug for connecting the user battery cabinet.
(3) Do not connect the UPS to any load yet. Then, connect the power cord of the
UPS to supply utility power to the UPS to make the UPS operate in utility power
mode.
(4) Connect the plug of the external battery cord to the external battery socket on
the rear panel of the UPS to complete the connection procedure and the UPS
will start to charge the battery pack.
The unit without CE markings—
(1) Use the battery pack with voltage: 36Vdc for 1 KS (3 pcs of 12V batteries),
96Vdc for UPS T2 000S/ 3 000S (8 pcs of 12V batteries). Connection of
batteries more than or less than required will cause abnormality.
(2) One end of the external battery cord is a plug for connecting the UPS and the
other end has 3 (or 2) open wires for connecting the battery pack.