  FAULT CODES

Faults 

Possible reasons 

Troubleshooting

Charging LED  

Solar array 

Check that solar and battery wire connections are 

indicator off during  

disconnection 

correct and tight. 

daytime when  

sunshine falls on  

solar modules 
Green Battery LED  

Battery voltage higher  Check the battery voltage. If voltage levels are high, 

indicator fast  

than over voltage 

disconnect the solar module immediately and 

flashing 

disconnect voltage 

change to a new controller. 

 (OVD) 
Battery LED  

Battery under voltage  Load output is normal. Charging LED indicator will 

indicators orange 

 

return to green automatically when fully charged.

Battery LED indicators   Battery over 

The controller cut off the output automatically.  

RED color and loads   discharged 

LED indicator will return to green automatically 

not working  

 

when not working. 

 

Load status  

Over load 

Remove or cut out the additional load and press 

indicator red and 

  

the  button, the controller will resume after  

slow flashing 

 

3 seconds.

Load status indicator   Short circuit 

Clear short circuit and press the button, the controller 

red and fast flashing   

will resume to work after 3 seconds.

All LED indicators  

Temperature of 

When heat sink of the controller exceeds 85°C, the 

flashing (battery  

controller too high 

controller will automatically cut input and output 

orange indicator  

 

circuit. When the temperature reaches below 75°C,  

flashing) 

 

the controller will resume operation. Reduce the  

 

 

environment temperature, the power of solar  

 

 

module or the power of the load.

All LED indicators  

System voltage error 

Check whether the battery voltage matches the 

flashing (battery red    

controller working voltage. Please change to a suitable 

indicator flashing) 

 

battery or reset the working voltage. If there is 

 

 

nothing abnormal, please press load button to 

 

 

clear the malfunction.

SOC value incorrect 

Wrong battery type  

Correct the right battery type; 

 

selected using the  

Using the configuration of the charging voltage 

 

reconfigured profile  

compensation if choosing the user defined battery 

 

of the user defined  

type and ignore the SOC. 

 

battery type. 

SPECIFICATIONS

Electrical Parameters

Nominal System Voltage  

12/24VDC

Max. PV input voltage 

50V

Max. Battery Terminal Voltage 

34V

Rated Battery Current 

SC320: 20A, SC330: 30A

Charge Circuit Voltage Drop 

0.28V

Discharge Circuit Voltage Drop 

0.20V

Self-consumption 

8.4mA/12V; 

7. 8mA/24V

Temperature compensation coefficient 

-3mV/°C /2V (Default)

Grounding 

Positive grounding 