Orientation
5
•
The pump direction-of-flow arrow faces the opposite direction to the system flow.
•
The pump cartridge is always horizontal.
•
Do not position the flow-switch on the underside of the pipe.
•
For vertical flow applications, only mount flow-switch where up-flow conditions exist.
FLOW-SWITCH ON UNDERSIDE OF PIPE
PUMP NOT HORIZONTAL