Progressive Dynamics PD52 Series Скачать руководство пользователя страница 4

Consult a licensed electrician or RV technician for installation assistance 

 

Specifications

(Specifications subject to change without notice) 

Model

 

PD52_ 

PD52DCS_ 

PD53 

Voltage Rating 
Current Rating (line) 
Current Rating (neutral) 
Dominant Source 
Open Neutral Protection 
Reverse Polarity Protection 
Safety Interlocks 
Under Voltage Protection 
Over Voltage Protection 
Multimode Surge Protection 

Surge Energy Rating 
Surge Current Rating 

Weight 
Dimensions 
Listed 

120/240Vac 

50A 
70A 

Generator 

No 
No 

Mechanical & Electrical 

No 
No 
No 
n/a 
n/a 

7 lbs 

10.38L x 6.88W x 4.50H 

Yes 

120/240Vac 

50A 
70A 

Generator 

Yes 
Yes 

Mechanical & Electrical 

Yes 
Yes 
Yes 

3,300 Joules 

103,000A 

10 lbs 

10.25L x 8.25W x 5.50H 

Yes 

120/240Vac 

100A 
100A 

Generator 

No 
No 

Mechanical & Electrical 

No 
No 
No 
n/a 
n/a 

17 lbs 

12.00L x 10.00W x 6.00H 

No 

 

TROUBLESHOOTING GUIDE 

 

 

PROBLEM

 

POSSIBLE CAUSES

 

ACTION

 

No Output when 
Plugged into Shore 
Power 

Wiring error between shore power and the transfer 
switch. 

Correct wiring 

Defective transfer switch 

Replace transfer switch 

Wiring error between generator and the transfer 
switch 

Correct wiring 

Generator malfunction 

Have generator serviced 

No Output when 
Generator is Running 

Wiring error between generator and the transfer 
switch. 

Correct wiring 

Generator malfunction 

Have generator serviced 

Defective transfer switch 

Replace transfer switch 

No Output to Auto 
Generator Start 

Wiring error between shore power and the transfer 
switch. 

Correct wiring 

Bad voltage sense control board. 

Replace control board 

Red LED(s) Illuminated 

(surge protected models only)

 

Surge protection has been damaged and is no longer 
functional. 

Replace control board assembly.   

(Contact Progressive Dynamics service department for correct control board assembly)

 

 

 

 

See website 

www.progressivedyn.com

 for more troubleshooting information and return instructions 

 

 

 

NOTES:  

Содержание PD52 Series

Страница 1: ...AVINGS LOSS OF USE OF ENJOYMENT OR OTHER INCIDENTAL DAMAGES ARISING OUT OF THE USE OF OR INABILITY TO USE THE PRODUCT THIS INCLUDES DAMAGES TO PROPERTY AND TO THE EXTENT PERMITTED BY LAW DAMAGES FOR PERSONAL INJURY THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE IV PROOF OF PURCHASE A warranty claim must be accom...

Страница 2: ...RE NOT DESIGNED FOR USE WITH 240 VOLT SINGLE LEG SUPPLIES APPLICATION OF VOLTAGES IN EXCESS OF 130 VOLTS FROM HOT TO NEUTRAL MAY CAUSE PERMANENT DAMAGE TO THE UNIT The 5200 5300 Automatic Transfer Switches can be installed as shown in figures 1 and 2 provided there is room to route the shore power generator and distribution connection wires The 5200 5300 Automatic Transfer Switches including the R...

Страница 3: ...he HOT1 side must be used for the control circuitry to work For models with surge protection both HOT1 and HOT2 must have power applied for proper operation HOW TO DISABLE GENERATOR TIME DELAY PD52DCSD REMOTE DISPLAY PD52 53 CONTROL BOARD To DISABLE the time out function of the control board INSTALL a 100 jumper of the connector at J1 PD52DCS CONTROL BOARD To DISABLE the time out function of the c...

Страница 4: ...ING GUIDE PROBLEM POSSIBLE CAUSES ACTION No Output when Plugged into Shore Power Wiring error between shore power and the transfer switch Correct wiring Defective transfer switch Replace transfer switch Wiring error between generator and the transfer switch Correct wiring Generator malfunction Have generator serviced No Output when Generator is Running Wiring error between generator and the transf...