5
WARNING:
All wiring must be installed by a certified electrician
according to the electrical safety.
The ceiling heater must be grounded in accordance with all national
and local building codes.
WARNING:
To reduce the risk of fire, do not store or use gasoline
or other flammable vapors and liquids in the vicinity of the heater.
All Wiring procedures and connections shall be in accordance
with the national and local codes having jurisdiction.
NOTE: Compatible with a 240V Line Voltage Double Pole Wall
Thermostat. Must be installed by a Certified Electrician.
Before installation:
Disconnect the main supply connection.
Supply cables shall be 10 AWG (5.3 mm2) copper wires
.
The heater must be connected to individual branch circuit protected
by 30 Amp circuit breaker only.
Supply cables must be equipped with a dual pole circuit breaker
rating at least 240V 30A/pole as main cutoff switch of power
connection to the heater.
CAUTION:
High temperature, risk of fire, keep electrical cords,
drapery, furnishings, and other combustibles at least 3 feet (0.9 m)
from the front of the heater and away from the side and rear.
WARNING:
To reduce the risk of fire, do not store or use gasoline
or other flammable vapors and liquids in the vicinity of the heater.
INSTALLATION INSTRUCTION:
1. Keep the unit at least 6 feet (1.8 m) away from the floor. This
minimum distance must be maintained.
2. Do not install closer than1 foot (or 0.3 m) to any adjacent vertical
surfaces or walls.
3. Keep at least 4.5 inches (11.5 cm) from the back wall (with or
without using the wall hanging mounting bracket).
INSTALLATION INSTRUCTIONS