QUICK GUIDE for 4 modules
www.profort.com
Pg.
3
Set-up with text message
1234 = password, 0 = zero, space counts as a character and is therefore important.
Define the unit
phone number and
change password, if
necessary. Add ID
text.
1234 N0 88888888 yyyy
ID text
(N0 = N + zero)
1234=current password, N0, 88888888= the unit
mobile no.
yyyy = new four-digit password.
ID text: First text in all messages from unit (max.
32 characters).
Receivers
Add
1234 N1 11111111
1234 N2 11111111 *
Adds receiver 11111111 in space no. 1 to receive
alarm as text message.
Adds receiver 11111111 in space no. 2 to receive
alarm as call with tones.
Further spaces (25 in all):
N2..N9, NA (10), NB (11) .. NP (25),.
Delete
1234 N1
Deletes receiver in space no. 1
Text on input
Add
1234 A0 OPEN TEXT
TEXT on input 0 by open/break. x = (A0…A2)
1234 L0 CLOSE TEXT
TEXT on input 0 by close/make. (L0..L2)
Delete
1234 A0
Deletes TEXT for input 0 by open/break.
(A0..A2)
1234 L0
Deletes TEXT for input 0 by close/make.
(L0..L2)
Only alarm if text
is added
1234 CT
The unit ignores input that has no text attached.
Add analog input
1234 V1 S yyyy zzzz
Set-up of the scale (yyyy = zzzz):
0-10 V (DIP-switch 1=ON) 0 10
0-20 mA. (DIP-switch 2=ON) 0 20
4-20 mA. (DIP-switch 2=ON) -5 20
PT100. (DIP-switch 3=ON) -309 115
Profort PTC. (DIP-switch 4=ON) -132 63
Add 2 alarm points
1234 V1 M 5 30
The unit sends alarm e.g. when temperature passes
5 and 30°C.
Add text in LOW
interval
1234 V1 A LOW TEMP
Alarm text in LOW interval (below 5°C).