SYSTEM FUNCTION PRINCIPALS 

 
 

LINE DIAGNOSTIC 

 

PRO EVAC system is a modular system, for each line there is a  zone card to be inserted in the 
commutation unit   
Diagnostic system  inserts in the amplifying  chain at regular interval of 1” an unheard  pilot tone of 
22 KHz. At the amplifier output and at end line loudspeaker, the tone pilot  survey is done in a 
constant way. In case of this pilot tone  absence, the system acts as follows: 

 

1)  Tone pilot absence  from the amplifier output ( amplifier default) . 

− 

The default indicator on the commutation unit  display is switched on  

− 

Main unit default sound  signal activation( buzzer). 

− 

Main unit and microphone stands display amplifier default. 

− 

The event  is memorised  in event log memory and in eventual print purposes when 
available. 

− 

Loudspeakers line commutation to back up amplifier – if back up amplifier available- 

 

2)  Tone pilot absence at end loudspeakers line (Line default). 

− 

The default indicator of the commutation unit front panel is  switched on. 

− 

Main unit default sound signal activation (buzzer). 

− 

Main unit and microphone stands display line default . 

− 

The event is memorized in event log memory and in eventual (when available)  print 
purposes . 

 

BACK UP AMPLIFIER 

 

PRO EVAC system is designed to connect one or two back up amplifiers to each commutation unit 
When only one spare amplifier is connected  (SPLIT OFF) all zones modules inserted in the 
commutation unit – in case of default- commute audio input and loudspeakers line to the same 
amplifier. Statistically it is improbable that two amplifiers are in default contemporaneously. But to 
remedy  it is necessary to define the back up amplifier to ensure the zones/line necessary power  
connect 100V output to terminal BCK 1 OUT and  bridge  BCK 1 OUT with  BCK 2 OUT. 
To ensure a good power repartition – in case of amplifier default- it is possible to connect 2 back 
up amplifiers (SPLIT ON). In this case the commutation unit is subdivided in 2 groups s of modules  
In case of zone 1 to.. 4  amplifier default the loudspeakers lines will be commuted to the first spare  
amplifier . In case of zone 5 to ..8 amplifier default , the loudspeakers line will be connected to the 
second spare amplifier. 

 

It is necessary to foresee at least one back up amplifier for each commutation unit installed. 

 

It is necessary to reset the system – accordingly to EN 60849 rules- and because the default signal 
persists-  even if the operating continuity is  ensured  because the loudspeakers line are connected 
to back up amplifier . 

 

The zones modules survey the  amplifier default and commute to the back up amplifier, but are not 
considered by programming purposes. Zones modules are involved only  by general or non 
selective  call.  

Содержание PRO EVAC SYSTEM

Страница 1: ...Evacuation system EN60849 CEI100 55 SYSTEM MANUAL ...

Страница 2: ......

Страница 3: ...Generalities Pag 15 Input output signal connections e Pag 15 Options Pag 15 Technical Characteristics Pag 16 Functions and Control Pag 16 EV BMH Generalities Pag 17 Power Supply Pag 17 Input output signal connections Pag 17 Technical Characteristics Pag 18 Functions and Control Pag 18 EV MFIRE Generalities Pag 19 Power supply Pag 19 Input output signal connections Pag 19 Technical Characteristics ...

Страница 4: ...gly to emergencies risk levels To apply to such standards the PA systems for sound paging and music diffusion must have the following features Mixer amplifiers control Loudspeakers line efficiency distribution in the various zones involved by the main system Manual and automatic alarm message diffusion Emergency microphone stand VV FF control Spare amplifier activation in case of amplifier default...

Страница 5: ...it for level noise measurement and for automatic volume control EV BMH Standard microphone stand for general call and for zones call EV MFIRE Emergency microphone stand fireman call station AUP120R AUP240R AUP480R AUP4150 4250 Power units for diffusion at constant voltage 100V CS6TALEN PR10TALEN TR15TALEN UPSPRO1000 UPSPRO2000 UPSPRO3000 Loudspeaker at 100 V constant voltage UPS Unit ...

Страница 6: ...or two back up amplifiers to each commutation unit When only one spare amplifier is connected SPLIT OFF all zones modules inserted in the commutation unit in case of default commute audio input and loudspeakers line to the same amplifier Statistically it is improbable that two amplifiers are in default contemporaneously But to remedy it is necessary to define the back up amplifier to ensure the zo...

Страница 7: ...oop wire In this way it is possible to check eventual interruptions due line short circuit as stated in point j paragraph 5 3 of EN 60849 standards The line circuit default survey is effected by the diagnostic system but there is no commutation in case of line interruption short circuit The loudspeakers connected to the line section continuously connected to the zone module are powered normally fo...

Страница 8: ...one line Input with priority for emergency call station VV FF 2 audio inputs Tuner CD Tape etc One audio input for advertisements message sources One audio input for central telephone call One slot for pre recorded messages card insertion 4 programmable audio outputs for music and messages diffusion One RS232 serial for PC connection purposes 6 inputs for remote contact of alarm fire central or si...

Страница 9: ...nd on any other audio source in function The connections are through UTP CAT5 AUX 1 Plug RCA stereo mixed is used for audio source for music diffusion Throughout a PC it is possible to set in which zone connect to this input the signal audio must be sent AUX 2 Plug RCA stereo mixed is used for audio source connection for music diffusion Throughout a PC it is possible to set to which zones the audi...

Страница 10: ...selection alarm message cancellation The balanced inputs not used must be maintained closed through a THECHNICAL CHARACTERISTICS B d 9 Y T I L I B I S N E S T U P N I X U A m h o K 0 2 E C N A D E P M I T U P N I X U A B d 0 T U P N I Y T I L I B I S N E S 2 G S M m h o K 0 2 T U P N I E C N A D E P M I 2 G S M I B d 0 Y T I L I B I S N E S T U P N I L E T m h o K 0 2 E C N A D E P M I T U P N I L...

Страница 11: ...e 250mAT delay 11 REMOTE INPUTS inputs for alarm central or similar purposes connection 12 TEL audio input for telephone central 13 AUDIO BUS audio Bus output for unit commutation 14 AUX 1 audio input for audio source 15 AUX 2 audio input for audio source 16 MSG audio input controlled for advertisement or similar messages 17 EMG input with priority for emergency microphone stand 18 DATA BUS in out...

Страница 12: ...ppropriate software The commutation unit composition is as follows 8 slot for diagnostic module insertion Led for immediate visualisation of the zone module status Connection module with the central and the next units Connection module for back up amplifiers 1 o 2 Power supply 230Vac POWER SUPPLY This apparatus main power supply 230Vac 50 60Hz In case when switched there is no signal check protect...

Страница 13: ... for balanced audio Low frequency signal connection between commutation unit and back up amplifier BCK 2 IN Terminal Euroblock to extract 3 ways for Low frequency balanced signal connection between commutation unit and next back up amplifier BCK 1 OUT Terminal Euroblock to extract 2 ways for 100V audio feedback signal between the first back up and the commutation unit BCK 2 OUT Terminal Euroblock ...

Страница 14: ...the next commutation input 15 AUDIO IN audio Bus input in receipt from main unit AUDIO BUS 16 AUDIO LINK audio Bus output towards AUDIO IN commutation unit and next commutation unit input 17 EV SCDIA diagnostics zone module Fig 2 ON BCK OFF RELAY AMP IN C NC NO GND LOOP SPKR AMP OUT REMOTE CONTROL ON BCK OFF RELAY AMP IN C NC NO GND LOOP SPKR AMP OUT REMOTE CONTROL ON BCK OFF RELAY AMP IN C NC NO ...

Страница 15: ...inal EUROBLOCK to extract 3 ways to use for audio balanced Low frequency signal to connect between the zone module and the amplifier zone AMP OUT Terminal EUROBLOCK extract 3 ways to use for 100V feedback audio signal to connect between the zone amplifier and zone module SPKR LOOP Terminal EUROBLOACK to extract 4 ways to use for 100V audio loudspeakers line Loop cable from the last loudspeaker lin...

Страница 16: ...D FUNCTIONS Fig 3 1 RELAY NC NA Relay contact max 24Vdc 1A for calls and messages activation 2 AMP IN Low frequency audio output to connect to amplifier zone 3 LOOP input for 100V audio loudspeakers feedback line 4 SPKR 100V audio loudspeakers line 5 AMP OUT 100V audio input to connect to zone amplifier output 6 BCK switch to back up operating mode activation 7 REMOTE CONTROL input for peripheral ...

Страница 17: ...tion Double plug Bus for digital line data receipt and next microphone stand data sending Dip Switch internal for numerical stand configuration Plug for external power supply POWER SUPPLY Microphone stand can operate in DC or AC and is supplied with a power supply 230Vac 12Vdc Close to the stand ensure to foresee a main 230Vac plug INPUT OUTPUT SIGNAL CONNECTIONS MIC BUS Plug RJ12 6 6 are used for...

Страница 18: ...ions L x H x D Microphone asta lunghezza Weight KEYS AND FUNCTIONS Fig 4 1 DISPLAY LCD rear illuminated 16x2 for basic functions visualisation 2 PWR Led power indicator 3 BUSY busy Bus led indicator 4 0 9 numerical keyboard for zone or area no entry to call 5 AREA selection key for area call selection 6 ZONE selection call for zone selective call 7 GENERAL CALL General call selection key Fig 4 Fig...

Страница 19: ...h for security block for operating mode selection PROEVAC SYSTEM CAN INVOLVE ONLY ONE V V FF EMERGENCY CONSOLE POWER SUPPLY The microphone stand is supplied with a power supply 230Vac 12Vdc It is necessary to foresee a plug close to the main 230Vac power supply In case of a black out stands emergency operating mode EMG ensures a direct power supply through Priority Bus connection to the main centr...

Страница 20: ... 1 DISPLAY LCD rear illuminated 16x2 to visualise the basic functions 2 PWR Power LED 3 BUSY Busy led indicator when the Bus is busy because for current calls from other sources 4 0 9 numerical keyboard compose zones or area corresponding no 5 AREA Selection key for area selection call 6 ZONE key for zone selection call 7 GENERAL CALL general call selection key 8 MIC Led for active microphone stat...

Страница 21: ... including Backup ones 2 Power commutation unit EV COMX 3 power central unit EV UNCE TO switch off the system effect contrarily the sequence 1 switch off EV UNCE 2 switch off the commutation unit EV COMX 3 switch off the amplifiers The tone pilot control can be modified in case the amplifier volume is very low Therefore ensure that the amplifier volume are set not below half level volume When the ...

Страница 22: ...it and default status setting Setting from the panel Press Enter ENT when the display visualise system status OK you can access to the different functions The functions are cyclic for each Enter key press To modify value data use fleche keys display modification has an effect on following press ENTER key Programmable functions throughout PC serial input are as follows Alarm reset Zone module scan ...

Страница 23: ...the following menu is displayed VIS SCHEDE ZONA The next right shaft key pressing allows to visualise the status of the zones modules surveyed If the all the modules are perfectly working the relevant identification codes will be indicated The modules in alarm audio defect status are GA indicated the matrix in alarm for module defect status are GS indicated Once the module scan is effected the sys...

Страница 24: ...ug realized for both lines standard line as well as for emergency line The microphone stand is keyboard equipped Keys are numbered from 0 to 9 plus 3 keys for calls For general call press and keep pressed General call key The ring lights up and display visualises CONNECT indicating the microphone activation If the line is busy with another call the display visualises BUSY The Led BUSY lights up If...

Страница 25: ...idered zone or in an area or all zones To activate a recorded voice message to diffuse it in a considered zone in a considered area or in all zones and to display on the microphone stands a text message To display a text message on microphone stands alarm reset The balanced inputs not used must be maintained closed through a resistance of 2 2Kohm whilst the unbalanced inputs 5 and 6 must be closed...

Страница 26: ... the emergency microphone stand Along with the diffusers line amplifiers and emergency microphone stand control the system is designed to ensure further diagnostic and default indication Specific default for zone module Internal voice message card default Microphone stands communications decoder default Audio Bus between central unit and commutation unit default FACTORY SETTING Each PROEVAC system...

Страница 27: ... CAT5 cable and RJ12 connector for EV MFIRE emergency microphone stand and EV BMH zones call details APPLICATION USE EXAMPLES 27 1 8 orange white orange green white blue blue white green brown white brown 1 2 3 4 5 6 7 8 1 8 1 6 orange black red green blue yellow 1 2 3 4 5 6 1 6 FEMALE PLUG MALE PLUG FEMALE PLUG MALE PLUG ...

Страница 28: ...28 NOTE ...

Страница 29: ...PROEL S p A Milan Offices via Walter Tobagi 30 Località Canzo 20068 Peschiera Borromeo Mi ...

Отзывы: