USER GUIDE 

KRM-X-1 & KRM-X-2 

6 (9) 

 

Produal Oy

 

Keltakalliontie 18, 48770 Kotka FINLAND 

Tel: +358 10 219 9100 / Fax: +358 5 230 9210 

[email protected] 

www.produal.com

 

Information is subject to change without prior notice. 

DISPLAY AND OPERATION 

A.  Smoke alarm (red). 
B.  Failure (yellow). 
C.  Alarm (red) and alarm/reset button. 

Failure reset: briefly press button and release. 
Alarm reset: Press button for at least 2 seconds until 

the red light goes out. 

D.  Display indicator (contamination in % or status). 
E.  Power supply (green). 
F.  Air flow (blue) lights up when there is insufficient air 

flow 

 
 

Display 

Meaning 

Explanation 

 

Start / 

calibration 

Shortly after starting the software version is displayed (4 digits), e. g. 

00 then 20 = Software 0020. The BACnet versions are indicated with 

“bA”. At startup or after a power failure, this is followed by a rotating 

segment display. 

 

Contamination in 

Flashes starting at 70 % (contamination relay drops out). At 99 %, the 

alarm light illuminates. 

 

Failure 

e.g. Missing smoke detector, disrupted communication with the 

smoke detector, processor failure. 
Failure (B) and alarm (A) lights light up at the same time  
Troubleshooting: change the detector and confirm by pressing the 

alarm / reset button (C). 

 

all lights on 

the circuit 

board light 

up 

Confirmation of 

reset / new start 

Occurs when alarm/reset button (C) is pressed for more than 8 

seconds, or if bridge circuit/ terminal 9/10 is open (missing bridge 

circuit or remote reset). Display goes out after releasing the 

alarm/reset button or closing the bridge circuit between terminal 9 + 

10. 

00 – 99 

flashing 

Bus address 

Only appears with MOD/BAC versions after pressing the address 

buttons T3/T4 directly on the circuit board. 

 

Indicator 

lights 

Meaning 

Explanation 

Alarm / reset 

(red) 

Smoke alarm or 

failure

 

Reset after failure: 

Briefly press alarm / reset button. KRM-X immediately restarts

Reset after alarm: 

Press and hold the alarm/reset button for at least 2 seconds until the 

red alarm light in the button goes out. KRM-X will start again after 

releasing the button. If the alarm/reset light continues to flash while 

the button is pressed, the smoke detector is still filled with test 

gas/test spray/smoke and cannot be reset. In that case, blow out the 

smoke from the detector or wait. 

A

B

C

A

D

E

F

Содержание KRM-X-1

Страница 1: ...h height or diameter for air ventilation ducts monitored with the 600 mm long standard air collecting tube under the VdS approval DIBt certification The indicated airflow direction must be observed wh...

Страница 2: ...es compliance with operating and installation instructions We are not liable for losses due to inappropriate use Unauthorized manipulations or modifications of the device render the operating permit t...

Страница 3: ...very for attaching the plate to the duct A 4 When installing on a rectangular air duct fit the plate directly to the tube When installing on a circu lar air duct use KS X fitting plate B and rubber bu...

Страница 4: ...2 13 14 15 green 16 17 yellow blue Smoke alarm Smoke alarm Service signal Contamination red Test Reset 3 4 Power supply 230 Vac 1 2 Power supply 24 Vac dc Test Reset NC contact 9 10 11 12 13 14 15 gre...

Страница 5: ...simultaneously pressing of T3 and T4 The value is saved when two underscores appear on the display _ _ NOTE The current value is also saved after 6 seconds without a button being pressed TESTING THE S...

Страница 6: ...detector processor failure Failure B and alarm A lights light up at the same time Troubleshooting change the detector and confirm by pressing the alarm reset button C all lights on the circuit board...

Страница 7: ...mber must have been cleared and fault rectified MAINTENANCE AND REPAIR The smoke detector must be tested at least once a year in order to ensure that it performs reliably over long time periods Withou...

Страница 8: ...ner housing Check all seals 6 Assemble all parts The cover screw tightening torque is 1 2 Nm 7 Test system by triggering the smoke detector with test spray 9 14 8 Check with the operator about the fun...

Страница 9: ...air flow 4 NTC temperature value The value can be used to determine the ambient temperature The value is combination of the ambient temperature and self heating of the circuit board See the following...