Notes for Installation

1. Sensor leads must be kept separately from main voltage wires in order to avoid high frequency noise

induced. Separate the power supply of the loads from the power supply of the controller.

2. When installation the sensor shall be placed with the head upward and the wire downward; The evaporator

sensor must be installed between the fins of the evaporator in the area, where probably the ice is the
thickest. Don't place the evaporator sensor near the electric heater.

3. The temperature controller can not be installed in the area with water drops.

8. Lock parameters

In normal operating,press

button and hold for 10 seconds to lock the parameters if

OFF

displayed

(No

odification is allowed),or to unlock if ON is displayed. Parameter can be displayed only and can not

be modified if locked, but the adjustment of the set temp. is still active.(the factory default is ON

)

"

"

"

"

"

"

is

m

Function details

1. Temperature control

After the delay time,the compressor starts operating when cold room temperature

(set temp.+ Hysteresis),

and will be off when cold-room temperature

set temp.

To protect the compressor, it can re-start unless the time when the compressor stops every time is longer
than the delay time (Parameter E4).

2. Defrosting Functions

Electric heating defrost: The defrost LED and the heater turns on,

Hot gas defrost : The defrost LED and valve will turn on . When

the

stops. A

valve will turn off , compressor will restart-up,

Enter the defrost status: It defrosts and heats only if the temp. of the evap. sensor is less than the defrost
termination temperature (Parameter F3).
Exit the defrost status: When the temperature of the

Sensor is over the defrost termination temp.

or the defrost duration end ,it will exit the defrost status.
When the duration of defrost is se tot 00 , the function of automatic defrost will be cancelled.

3. Display during defrost

When setting the parameter F4=1, the room temperature is locked during defrost, and the last value before
defrost is displayed. When defrost ends, normal display will be resumed after 20 minutes delay of room
temperature display (or set temp.is reached). The defrost LED flashes during the delay.

4.

5. Abnormal work mode

When room sensor is short-circuited or overheated (more than

/

) HH is displayed; When room

sensor is open-circuiedt or

too low (less than

/

) LL is displayed. At that time

the compressor operates automatically by the cycle of 45 minutes on and 15 minutes off.
When evap. sensor fails or over the displayed range, the defrost termination will be just controlled by the
defrost duration. (Parameter F1)

6. Circuit Diagram

the compressor stops. The heater will be

disconnected after the defrost duration ends.After two minutes dripping time , it will exit the defrost status
and start the compressor. After two minutes delay time the evaporation fan will run.

the defrost duration ends,

compressor

fter two minutes delay the

after two minute the fan

will run.

evap.

set temp.

set temp.

120

temperature is

4

0

"

"

"

"

"

"

The alarm function

When the power is on and after the compressor turns off , the alarm function is set.

When the cold-room temperature is higher than (

+ C2) or lower than (

C3

, it will

alarm after the delay time(E4) and the display will flash. The buzzer will sound. The sound can be cancelled
by pressing random key.

45

5

4

℃ —

Accessories for the temperature controller

1. One attached transformer
2. Two temperature sensors
3. One installation stand
4. One cover panel and 1

3

10mm screw

φ ×

www.procoolmfg.com