background image

H - I - J

 

PROGRAMMER’S MANUAL 

V8.94.11-

 

 

- 36 -

 

Explanation of the logical functions 

start  switch:

 

continuous  start  command. If multiple inputs  are  programmed  as  start  switch,  they  are in logic  “AND” 

relation. 

start switch inverse:

 its function is the same as that of the start switch, but it starts the motor in the opposite of the 

appointed direction. 

start button:

 pulse type start command. If multiple digital inputs are programmed as start button, they are in logi

c “OR” 

relation therefore if any of them is activated the start command occurs! 

8

 

CAUTION 

If start is selected to more than one input at the same time, then starting and stopping the machine must be thoroughly 
considered regarding life protection! 

 

Start switches and push buttons can exist also mixed. In such case, all start switches have to be active for 
the possibility of giving out start command with any of the start push buttons! If in menu 

4-8-1

 the terminal 

regulation is enabled, then the start button of the terminal functions as start push button, therefore at starting 
from terminal only, start switch must not be selected to any of the inputs. 

If in menu ite

4-8-2

 regulation through CAN bus is activated, the start switches selected to the inputs will 

have  also  in  this  case  enabling  role  (they  will  be  in  „AND”  conjunction  with  the  start  command  arriving 
through the CAN bus). 

start push button inverse:

 its function is the same as that of the start push button, but it starts the motor in the opposite 

of the appointed direction. 

direction change switch:

 activation of the input acts as a command for changing the direction. If more than one input 

is programmed to direction change switch, then activation of any further input causes direction change.  

For example: 

with two digital inputs programmed to direction change switch: activation of both inputs means 

two direction change commands, that is, the original direction will be valid. 

direction  change  push button:

  pulse format  direction  change  command. If more than  one  input is  programmed to 

direction change push button, then they are in logical “OR” conjunction with each other. If any of them acts, the direction 
change occurs. If the direction change switch is also selected, the push buttons are ineffective. 

jog normal:

 used generally for adjusting the machinery, it starts the motor with the parameters set in menu 

8-4

. It is 

active from the stop state only, in the appointed direction. If the terminal regulation is enabled in menu 

4-8-1, 

also the 

jog button of the terminal activates the function, independently of the state of the jog input. 

jog inverse:

 used generally for adjusting the machinery, it starts the motor with the parameters set in menu 

8-5.

 It is 

active from stop state only, reversely to the appointed direction. 

external error:

 it makes the appliance run out with error message (e.g. motor thermal switch, emergency stop etc.) 

external event:

 

its activation causes writing “external event” in the event log, with the actual point of time. 

acknowledgement:

 means accepting the error messages, cancels the inhibition state. 

stop:

 effects stopping the motor according to the setting. 

emergency stop:

 serves the emergency stopping of the motor. The frequency converter stops the motor with the fall 

steepness set in menu 

3-13

. 

spin out:

 effects stopping the motor with spin out. When activated, the frequency converter lets the motor freely stop 

DC brake:

 effects stopping the motor with DC braking. When activated in stop state, with the emerging standing torque 

a hold function can be effected. 

f hold:

 inhibition of the frequency change. When activated, the frequency change stops even at rising and falling run! 

Содержание V3D Series

Страница 1: ...H I J frequency converters programmer s manual from software version V8 94 11 onwards P Since 1984...

Страница 2: ......

Страница 3: ...ick menu 16 Factory setting of the quick menu 17 1 Operation mode menu 18 Function of the modifying signal 21 PID regulation 22 Explanation of the parameters 23 Explanations to the PID regulations 23...

Страница 4: ...vities 64 Display image with big characters 65 11 System parameters menu 66 Parameter sets 66 Saving the parameter set 67 Loading up the parameter set 67 Exceptions at loading the parameters set 68 Mo...

Страница 5: ...safety measures warnings and instructions described in the manual Absolutely follow the safety notes described in the manual The operating company is responsible for any personal injury and property...

Страница 6: ...s assures that the 9 V supply voltage will still be sufficient for the externally connected terminal or the internal power supply of the display If the terminal is connected through a thicker cable an...

Страница 7: ...ipped with a 4x16 character display 11 push buttons as well as error and operating state signalling It can be used as a built in unit or in casing as a standalone unit The pane of the push buttons is...

Страница 8: ...the push buttons of the upper programming group With the push buttons of the upper group it can be moved between the menu items of the data setting and display data can be entered and the data to be...

Страница 9: ...fication User password For altering the parameter entering of the user password is necessary Setup password For altering the parameter entering of the setup password is necessary Manuf password For al...

Страница 10: ...s indicates the actual frequency converter The functions of the push buttons during display can be selected e g operating the motorized potentiometer changing the parameter displayed in row 4 etc In c...

Страница 11: ...Reading in programming mode first row the name of the parameter along with its main menu ordinal number e g 2 Control Tup second row the submenu ordinal number and the value of the actual parameter e...

Страница 12: ...Stop Display mode scrolling the displayed variables upward Programming mode moving in the menu upward Parameter setting increasing the value or scrolling the selector switches upward With selected ter...

Страница 13: ...s or relays two free programmable analogue output back indications two optionally four free programmable analogue input signals for regulation or control potentiometer voltage or current S curve type...

Страница 14: ...n on program update The manufacturer provides all users with the latest program version free of charge but they have to bring the frequency converter to the manufacturer s premises The new program is...

Страница 15: ...ut 11 9 language 11 10 CAN bus 11 12 terminal function 11 13 automatic error ackn 11 14 save event 11 18 manufacturing number 11 19 software version 11 20 date 11 21 currents 11 22 voltages 11 23 spec...

Страница 16: ...arts 1 rise time 1 control Tup 5 0 s Adopting parameters in the quick menu In programming mode each parameter can be adopted in the quick menu with button This is indicated by a sign after the number...

Страница 17: ...5 type dep type dependent A Parameter 4 8 1 f maximum fmax the highest frequency Even if the frequency reference signal is set to a higher value the fmax value is effective For V3D type equipment wit...

Страница 18: ...on reference signal if the source of the reference signal is the terminal 0 00 100 00 0 00 1 3 selection Permits the selection of the operation mode control regulation control 1 5 control Permits the...

Страница 19: ...peed m s speed m m speed km h volume l volume m3 revolution rpm pressure bar pressure Pa temp C frequency Hz user 1 user 2 frequency Hz 1 6 regulation Permits the settings of the parameters used with...

Страница 20: ...ssure of the compressed air will be measured with a remote transmitter and the control occurs to this pressure If the 100 reference signal corresponds to 20 bar pressure then after setting the corresp...

Страница 21: ...absolute change made by an active input 0 00 300 00 0 00 1 8 6 gradient normal The value of the modification related to 100 Hz or 100 ref sig The value of the modification related to the reference sig...

Страница 22: ...the PID parameter set to be used 1 10 1 selection In regulation mode this PID parameter setting will be valid PID1 PID2 PID3 PID4 frequency dep PID1 1 10 2 change over points The change over frequenc...

Страница 23: ...tion the correct adjustment of the IRE is very important This applies to the IRE parameters and the wiring too If the IRE measures not the rotation of the motor shaft but some decreased or increased r...

Страница 24: ...hints P proportional For simple regulations e g fluid level regulation it is practical to use proportional regulation Thus the set in process is the fastest and there is no tendency to swinging The r...

Страница 25: ...2 1 rise time It means at both control and regulation the limitation of the slope of the frequency rise 2 1 1 control Tup 0 05 3276 7 5 00 s 2 1 2 regulation Tup 0 05 3276 7 5 00 s 2 1 3 referencing...

Страница 26: ...f2 f3 2 3 4 fourth breakpoint f3 f4 Effect of the S curve the same at acceleration and deceleration Submenu Explanation further submenus Values Default setting Unit 2 4 S curve It means the implement...

Страница 27: ...vention 2 7 2 time N 1 60 N s 2 8 start type normal Starts from 0 Hz flying Seeks the frequency necessary for operating the rotating motor In case of short voltage blackout especially with large flywh...

Страница 28: ...eans at both control and regulation the limitation of the frequency decrease slope In case of stop the fall time of the regulation acts even in control mode The time needed for reaching 0 Hz starting...

Страница 29: ...f2 f3 3 3 4 fourth breakpoint f3 f4 Explanation of the deceleration with breakpoints 3 5 stop type normal It means running down the frequency DC brake Switching a standing field to the motor mixed Co...

Страница 30: ...e g at fast deceleration the frequency converter limits the gradient of slope if it is needed for providing secure stopping If the resistor brake is enabled its operation is shown in the state displa...

Страница 31: ...the user provides the brake resistor the rating type and placement must be consulted with the manufacturer Example Rbrake 100 P Rbrake 200 W Ubrake 660 V P 660V2 100 4356W Overloading 4356 200 21 78 2...

Страница 32: ...input range in the percent of the whole range In this voltage current zone on start command the equipment is in waiting mode The start will be active again in a distance of the hysteresis from the sto...

Страница 33: ...0 V 4 1 3 2 lower 0 0 10 0 0 0 V 4 1 4 current Setting the upper and lower level 4 1 4 1 upper 0 0 20 0 20 0 mA 4 1 4 2 lower 0 0 20 0 0 0 mA 4 1 5 function Functions of the analogue IN1 input contro...

Страница 34: ...he fall time for the refe rence signal from fmax or from fnom to 0 In case of regulation the fall time for the reference signal from 100 to 0 In case of modification the fall time for the modification...

Страница 35: ...that of item 4 11 digital input 1 digital input 7 8 at VLD and VHD types only 4 18 digital input 8 4 21 virtual input 1 Similarly to the built up digital inputs with the use of the internal signal sel...

Страница 36: ...ange For example with two digital inputs programmed to direction change switch activation of both inputs means two direction change commands that is the original direction will be valid direction chan...

Страница 37: ...control can be made from the RS485 T connection During the activated state of the RS485 exchange the terminal connected to the RS485 T connector of the equipment cannot work CAN exchange this serves...

Страница 38: ...l input 5 0 sequence 1 3 for activating program groups menu 9 26 Explanation of other functions counter 3 F input for shifting the given counter upward counter 3 L input for shifting the given counter...

Страница 39: ...nal transmitters with different division will effect both the frequency and the rotation speed ratio For example if the master equipment uses a signal transmitter with 1000 divisions and the slave equ...

Страница 40: ...ointly For leaving any value unchanged without modification it has to be approved with the Enter button 4 30 2 1 multiplier 1 32000 1 4 30 2 2 divider 1 32000 1 4 30 2 3 dynamic Enables the marker adj...

Страница 41: ...ed regulations 0 6000 1500 f min 4 31 3 position 100 At position regulations 0 50000 1000 rot 4 31 4 position 0 Setting the basic position of the incremental signal transmitter given in menu 4 31 5 no...

Страница 42: ...the load At selecting rotation speed IRE the nominal value belongs to that rotation speed which was set as 100 at setting the IRE data Menu item 4 31 2 This is important because the parameter the IRE...

Страница 43: ...erage 100 Pbrake current 100 frequency Imotor Umotor Udc Unet Pinp control ref s mod cont ref s reg ref s mod reg ref s feedback error signal an IN1 an IN2 an IN3 an IN4 an IN1 2 an IN3 4 counter 1 co...

Страница 44: ...29 The parameters of the time intervals can be set in menus 5 26 5 27 5 28 PID extension 3 at VLD and VHD types only N ready start stop forward brake rel compare 1 compare 2 compare 3 error code MOD...

Страница 45: ...evel pulse extended level 5 16 2 take effect The parameter the timer should have effect on In case of selecting a digital output e g pulling of a relay can be delayed and also its operating time can b...

Страница 46: ...alogue IN 1 2 3 4 10V 20mA counter 1 2 3 10000 run time 1 2 1000h heatsink 100 C n n sync n ENC n 100 4 31 2 torque Mn Pbrake average 100 Pbrake current 100 frequency Imotor Umotor Udc Unet Pinp contr...

Страница 47: ...o 5 26 1 2 hour 0 23 0 5 26 1 3 minute 0 59 0 5 26 1 4 second 0 59 0 5 26 2 off 5 26 2 1 day no every day Monday Tuesday Wednesday Thursday Friday Saturday Sunday weekdays no 5 26 2 2 hour 0 23 0 5 26...

Страница 48: ...too Similar settings can be applied to any comparator and digital output comparator 1 mode window comparator 1 source frequency at comparator 1 value 1 value 2 and the hysteresis set according to dem...

Страница 49: ...pendent A 6 5 nn nominal rotation speed The rotation speed at nominal load At the displays it can be used as orientation data in function of the load 100 30000 1450 f min 6 6 cooling type For the ther...

Страница 50: ...nding motor can be performed anytime no standing rotating no 6 11 R stator meas In vector mode 6 28 mode after giving start should the equipment perform a dc stator resistance measurement or not The m...

Страница 51: ...cing the frequency the motor runs more silently around 50 Hz it runs more quietly but the available torque slightly decreases 0 0 100 0 50 0 6 16 linearity of the magnetizing current Specifying the ma...

Страница 52: ...otor sinusoidal is set to No 6 23 1 U spare Reference signal belonging to the drive 80 120 90 6 23 2 drive regulation 6 23 2 1 proportional effect 0 30000 100 6 23 2 2 integrating effect 0 3000 100 6...

Страница 53: ...ncy control encoder Field oriented drive with incremental rotation speed signal transmitter vector Field oriented drive without signal transmitter U f FOC Sensorless U f Procedure of the empirical set...

Страница 54: ...consideration using the heat limit E g the 120 heat limit puts each point of the curve upwards by 20 Permissible motor overcurrent vs time a motor power below 3kW b motor power between 3 kW and 20kW c...

Страница 55: ...Here the state between linear and quadratic characteristic can be set according to demand At 0 linear at 100 quadratic 0 100 0 7 3 user characteristic Creating an arbitrary voltage vs frequency chara...

Страница 56: ...ency limits 0 fmax the voltage values 0 Umax can be set Frequencies f1 f2 f3 f4 f5 f6 Voltages U1 U2 U3 U4 U5 U6 Beyond fn the voltage takes up the value U6 The frequency value which does not fulfil t...

Страница 57: ...al Low frequency discontinuous operation mode in the actual direction used generally for adjustment of the machinery Independently of the selection of the operation mode regulation or control it can b...

Страница 58: ...9 1 counter 1 i If a program is selected as sequence cycle its cycle counter will be the counter with identical number 9 1 1 type The actual value of the counter corresponds to the commands of the up...

Страница 59: ...Finishing the programs releases also stop normal stop normal 9 11 program 1 Enabling the program 1 setting the program parameters level The lower is the number of the program the higher is its priori...

Страница 60: ...e inhibitory condition prevents it e g change of the activating input the cycle counter got to zero other input causes interruption The cycle counter is always the counter with the number identical wi...

Страница 61: ...t returns to the default setting according to the menu item end it stops or repeats cyclic The commands stop spin out and DC brake can stop the operation Example for activating from the terminal block...

Страница 62: ...voltage calculated power consumption control reference signal modified control ref signal regulation reference signal modified regulation ref signal regulation feedback signal error signal analogue IN...

Страница 63: ...spin out or continuous spin out command from digital input Stop Appears in case of stop during the run down of the frequency f hold Frequency change inhibited e g from digital input Jog Jog command i...

Страница 64: ...ack 100 error signal 100 analogue IN 1 2 3 4 10V 20mA analogue IN 1 2 3 4 10V 20mA counter 1 2 3 10000 run time 1 2 1000h heatsink 100 C n n sync n ENC n 100 4 31 2 torque Mn Pbrake average 100 Pbrake...

Страница 65: ...size If the row to be displayed cannot be written in maximum 4 characters dimension format e g status dig IN etc the big character display is not available no yes no i In case of big character displa...

Страница 66: ...g another application When loading from terminal even the whole parameter set or a part of it can be uploaded from another equipment 11 1 1 1 memory The parameter sets stored in the equip ment can be...

Страница 67: ...minal then only that setting can be overwritten More than one parameter set with the same name cannot be saved in the programmer terminal at the same time terminal 1 terminal 2 terminal 3 terminal 4 t...

Страница 68: ...ng not only complete parameter sets but also for modifying certain parameters only based on the saved parameter set Whether to load the complete parameter set or only a part of it can be set in menu 1...

Страница 69: ...ded to or removed from the quick menu or the user macro At each switch on the equipment goes in the editing quick menu mode quick menu user 1 user 2 quick menu 11 4 3 copy This copies one macro into t...

Страница 70: ...frequency is necessary at mixed The modulation is symmetrical below and flat top type above type dep 500 0 type dependent Hz 11 6 4 dead time compensation none Compensation switched off software Estim...

Страница 71: ...trol feedback s Application similar to PID extension with more frequency converters f inp f out ref signal feedback signal f out Explanations to the CAN bus At selecting master the CAN bus operates as...

Страница 72: ...ror acknow ledgement In case of error due to overvoltage overcurrent overload the equipment tries to acknowledge the error itself without external intervention This can be successful if the cause of t...

Страница 73: ...20 7 second 0 59 0 System parameters changeable with the manufacturer password Submenu Explanation further submenus Values Default setting Unit 11 21 currents This item permits the calibration of the...

Страница 74: ...assword Password can be assigned here to two priority levels the user level and the installer level The installer password permits of course also access to the parameters protected with user password...

Страница 75: ...hat can be stored mains switch off and on depending on the state of menu item 11 14 1 occurrence of start stop events depending on the state of menu item 11 14 2 occurrence of an external event from a...

Страница 76: ...total energy consumption E cons tot energy consumption E cons If only a display is connected to the equipment also the cause of the error is displayed in the lower row Pushing the Escape button menu i...

Страница 77: ...al regulation is not enabled but a stop command was given out from it Enabling the terminal regulation if necessary 1 An ref high An ref h The frequency converter senses the 10 V reference voltage hig...

Страница 78: ...omenon of output shorting Check the cabling and connections between motor and equipment 4 HW voltage prot HWvoltage Intermediate DC voltage has reached the maximum HW inhibit limit or the charging rel...

Страница 79: ...in processing the analogue inputs or several digital inputs Internal error The manufacturer is required to troubleshooting 7 Par CHKSUM err Par CHKS CHKSUM error of the parameter set If this error oc...

Страница 80: ...digital terminal blocks SD the frequency can be changed with the potentiometer connected to the analogue terminal blocks SA The lower extreme position of the potentiometer sets waiting mode Control fr...

Страница 81: ...reference signal maximum 80 1 6 3 2 regulation reference signal minimum 40 1 6 4 1 regulation reference signal acceleration 30 0s 1 6 5 1 regulation start stop time limitation 60s 1 6 5 2 regulation s...

Страница 82: ...4 31 1 IRE resolution 1000 4 31 2 IRE rotation speed 100 5000 6 5 nominal rotation speed 2920 8 1 f maximum 86 Hz 8 2 f minimum 1 Hz 8 3 frequency inhibit limit 105 Hz 1 11 1 PID 1 Ap proportional ga...

Страница 83: ...ce circuit jog command for starting at a low frequency e g for adjustment of the machinery master slave controlling unit subordinated unit memory 1 3 storage places for the user settings in the freque...

Страница 84: ...n one after another slip compensation load depending frequency correction for keeping the rotation speed constant start stop start command stop command stop band analogue input signal range at start t...

Страница 85: ...H I J PROGRAMMER S MANUAL V8 94 11 85 User settings Submenu Explanation Setting Unit...

Страница 86: ...H I J PROGRAMMER S MANUAL V8 94 11 86 Notes...

Страница 87: ......

Страница 88: ...ocon hu Internet www procon hu Issue January 2019 I II III IV V VIII IX X XI XII XIII XIV XV XVI XVII XVIII XIX XX XXI XXIII XXII B a r o s s u V c i t T m r u Nyitra u Tin di u Per nyi Zsigm ond u Ki...

Отзывы: