4.6. Setpoint Limiting
The Setpoint Limiting feature can be enabled using switch CONFIG 2-2.
When the switch is in the OFF position Setpoint Limiting is disabled.
When the switch is in the ON position Setpoint Limiting is enabled.
2-2
Setpoint Limiting
OFF Disabled
ON Enabled
Note:
Setpoint Limiting settings can be changed by writing to Modbus registers (see chapter 12.1 for more details).
4.7. Timeout
The Timeout feature can be enabled using switch
CONFIG 2-3
.
When the switch is in the OFF position the Timeout feature is disabled.
When the switch is in the ON position the Timeout feature is enabled.
2-3
Timeout Feature
OFF Disabled
ON Enabled
Note:
The timeout value can be changed by writing to a Modbus register (see chapter 12.1 for more details).
4.8. Input type selection
The input type for the four analogue inputs (
S.P, MODE, FAN SPEED, OCC MODE
) can be configured using switch
CONFIG 2-4
.
When the switch is in the OFF position inputs these inputs are set to voltage (0-10VDC) type.
When the switch is in the ON position inputs these inputs are set to resistive (
Ω
) type.
2-4
Analogue input type
OFF Voltage
(0-10VDC)
ON Resistive
(
Ω
)