www.usaprocom.com
200314-01D
20
Problem
Possible Cause
Corrective Action
ODS/pilot lights but flame
goes out when control
knob is released.
1. Control knob is not fully
pressed in.
2. Control knob is not pressed
in long enough.
3. Equipment shutoff valve is
not fully open.
4. Thermocouple connection is
loose at control valve.
5. Pilot flame not touching
thermocouple, which allows
thermocouple to cool, caus-
ing pilot flame to go out. This
problem could be caused by
one or both of the following:
A) Low gas pressure
B) Dirty or partially clogged
ODS/pilot
6. Thermocouple damaged.
7. Control valve damaged.
1. Press in control knob fully.
2. After ODS/pilot lights, keep
control knob pressed in 30
seconds.
3. Fully open equipment shutoff
valve.
4. Hand tighten until snug, and
then tighten 1/4 turn more.
5. A) Contact local natural or
propane gas company
B) Clean ODS/pilot (see
Care and Maintenance
,
page 18) or replace ODS/
pilot assembly
6. Replace thermocouple
7. Replace control valve.
Burner(s) does not light
after ODS/pilot is lit.
1. Burner orifice is clogged.
2. Burner orifice diameter is too
small.
3. Inlet gas pressure is too low.
1. Clean burner orifice (see
Care and Maintenance
,
page 18) or replace burner
orifice.
2. Replace burner orifice.
3. Contact local gas supplier.
Delayed ignition of
burner(s).
1. Manifold pressure is too low.
2. Burner orifice is clogged.
1. Contact local gas supplier.
2. Clean burner (see
Care and
Maintenance
, page 18) or
replace burner orifice.
Burner backfiring during
combustion.
1. Burner orifice is clogged or
damaged.
2. Burner is damaged.
3. Gas regulator is damaged.
1. Clean burner orifice (see
Care and Maintenance
,
page 18) or replace burner
orifice.
2. Replace burner.
3. Replace gas regulator.
Burner plaque(s) does
not glow.
1. Plaque is damaged.
2. Inlet gas pressure is too low.
3. Control knob set between
locked positions.
1. Replace burner.
2. Contact local gas company.
3. Turn control knob until it
locks at desired setting.
High yellow flame during
burner combustion
1. Not enough air.
2. Gas regulator is defective.
3. Inlet gas pressure is too low.
1. Check burner for dirt and
debris. If found, clean burner
(see
Care and Maintenance
,
page 18).
2. Replace gas regulator.
3. Contact local gas supplier.
TROUBLESHOOTING