Page - 6
10. Reset Password
l
To go to next menu after annunciation press “Increment”.
l
The LCD shall display “Reset Password”.
l
Password can be modified by pressing “Enter”
l
ECON will request for the present password, after feeding correct
password change password will be requested and the password will be
replaced by new password on pressing start button..
Parameter Mode
Parameter Options/Limits Description
Default Setting
A.
System Parameter
System parameters are the parameters which are programmed once
during initial installation and does not require frequent changes. As these
are critical parameter and hence are password protected. It is possible to
view system parameter without knowing the password but editing is
possible only after entering correct password
All system parameters are listed below along with their default value and
minimum / maximum variation range. Values can be increased or
decreased by pressing up/start and down/stop button respectively . Next
parameter can be selected by pressing next button
Solenoid
Type
1: Pull to Start
2: Pull to Stop
Pull To Start
In this mode fuel solenoid
contact changes from Open
to Close at the time of
cranking and remains close
till the genset is running. For
stopping the generator this
contact opens.
Pull To Stop
In this mode fuel solenoid
contact remains open at the
time of cranking and till the
genset is running. For
stopping the generator this
contact closes for a user
programmed time.
Pull to Stop
Operating Instructions