       WARNING:   Rework   worksheet,  adding
the  space  of   the  adjoining  unconfined
space.  The  combined   spaces  must   have
enough  fresh air  to supply  all  appliances  in
both  spaces.

If  the actual  Btu/Hr  used  is  less  than  the  maximum  Btu/Hr  the  space  can  support, the  space  is  an
unconfined  space. You  will  need  no  additional  fresh  air  ventilation.

3. Add  the  Btu/Hr of all fuel burning appliances in the space.

     Vent-free heater                                                       Btu/Hr
     Gas water heater*                                                    Btu/Hr
     Gas furnace                                                             Btu/Hr
     Vented gas heater                                                   Btu/Hr
     Gas heater logs                                                       Btu/Hr
     Other gas appliances* +                                          Btu/Hr
    Total                                =                                        Btu/Hr

    *Do  not  include  direct-vent  gas  appliances. Direct-vent  draws  combustion  air  from  the  outdoors  and
       vents to the outdoors.
4. Compare  the  maximum  Btu/Hr  the  space  can  support  with  the  actual amount of Btu/Hr used.
                          Btu/Hr (maximum the space can support)
                         Btu/Hr (actual amount of Btu/Hr used)
         

Example

 :  51,200 Btu/Hr(maximum the space can support)

                           56,000 Btu/Hr(actual amount of Btu/Hr used)
The  space  in  the  above  example  is  a  confined  space  because  the  actual  Btu/Hr  used  is  more  than  the
maximum  Btu/Hr  the  space  can  support.
You  must  provide  additional  fresh  air.  Your  options  are  as  follows:
A.  Rework  worksheet, adding  the  space  of  an  adjoining  room. If  the  extra  space  provides  an  unconfined
space, remove  door  to  adjoining  room  or  add  ventilation  grills   between  rooms. 

See  Ventilation  Air  From

Inside  Building (below)

.

B.  Vent  room  directly  to  the  outdoors. See  

Ventilation  Air  From  Outdoors

 (below).

C.  Install  a  lower  Btu/Hr  heater, if  lower  Btu/Hr  size  makes  room  unconfined.

Figure  2 -Ventilation  Air  from  Inside  Building

 Example:
 Gas  water  heater          30,000        Btu/Hr
 Vent-free  heater    +      26,000        Btu/Hr
 Total                         =     56,000        Btu/Hr

         WARNING:  If  the  area  in  which  the  heater  may  be  operated  is  smaller  than  that  defined  as  an  unconfined
space or  if  the building  is  of  unusually  tight  construction, provide  adequate  combustion  and  ventilation air by  one
of   the  methods  described  in  the  

National Fuel  Gas  Code, ANS  Z223.1, Section  5.3 

 or  applicable  local  codes.

This  fresh air  would come  from an adjoining  unconfined
space.  When  ventilating  to  an  adjoining unconfined
space, you  must  provide  two  permanent  openings: one
within 12

"

 of  the  ceiling  and  one  within 12

"

 of  the  floor

on  the  wall  connecting  the  two  spaces (see  options 1
and  2, Figure 2). You  can  also  remove  door  into
adjoining  room (see  option 3, Figure 2). Follow  the

National  Fuel  Gas  Code. NFPA  54/ANS  Z223.1,  Sec-
tion 5.3,  Air  for  Combustion  and  Ventilation

  for re-

quired size of  ventilation grills or ducts.

Ventilation  Air  From  lnside  Building

Ventilation  Air  From Outdoors

Provide extra fresh air by using ventilation grills or ducts.
You must provide two permanent openings: one within
12

"

 of the ceiling and one within 12

"

 of the floor. Connect

these items directly to the outdoors or spaces open to the
outdoors. These spaces include attics and crawl spaces.
Follow the 

National Fuel Gas Code, NFPA 54/ANS

Z223.1, Section 5.3, Air for Combustion and Ventilation

for required size of ventilation grills or ducts.

IMPORTANT:

 Do not provide openings for  inlet or outlet

air into attic if attic has a thermostat-controlled power vent.
Heated air entering the attic will activate the power vent.

Figure  3 -Ventilation  Air  from  Outdoors

Содержание BL28TYLA-C

Страница 1: ...supplier This appliance may be installed in an aftermarket p e r m a n e n t l y l o c a t e d m a n u f a c t u r e d mobile home where not prohibited by local codes This appliance is only for use w...

Страница 2: ...ee from combustible materials gasoline and other flammable vapors and liquids 1 This appliance is only for use with the type of gas indicated on the rating plate This appliance is not convertible for...

Страница 3: ...Figure1 Vent Free LP NG Gas Stove WATER VAPOR A BY PRODUCT OF UNVENTED ROOM HEATERS Water vapor is a by product of gas cmbustin An unvented room heater produces approximately one 1 ounce 30ml of water...

Страница 4: ...ON Determining if You Have a Confined or Unconfined Space Use this worksheet to determine if you have a confined or unconfined space Space Includes the room in which you will install heater plus any a...

Страница 5: ...room unconfined Figure 2 Ventilation Air from Inside Building Example Gas water heater 30 000 Btu Hr Vent free heater 26 000 Btu Hr Total 56 000 Btu Hr WARNING If the area in which the heater may be o...

Страница 6: ...coverings or operating heater where impurities such as tobacco smoke aromatic candles cleaning fluids oil or kerosene lamps etc in the air exist may discolor walls IMPORTANT Vent free heaters add mois...

Страница 7: ...nput adjustment NG Models 5 to 10 5 W C Gas supplier provide external regulator for natural gas INSTALLATION Continued WARNING Never connect heater to private non utility gas wells This gas is commonl...

Страница 8: ...ter and equipment shutoff valve to gas supply Check reconnected fittings for leaks Pressure Testing Heater Gas Connections 1 Open equipment shutoff valve see Figure 8 Figure 9 Checking Gas Joints CHEC...

Страница 9: ...Draw the four strand cable backward so as to expose the three black green white lines on the four strand cable at the back of rear panel Be sure not to drop the temperature controlled wire off the ref...

Страница 10: ...10 Installing Blower Accessory Blower Accessory Model PF06 YJLF F...

Страница 11: ...econds or less This will allow air to bleed from the gas system WHAT TO DO IF YOU SMELL GAS SEE WARNING on Page 2 for proper instructions C Use only your hand to push in or turn the gas control knob N...

Страница 12: ...Flame Pattern with Control Knob Set to High Flame Figure 17 Injector Holder On Outlet Burner Tube WARNING Turn off heater and let cool before cleaning CAUTION You must keep c o n t r o l a r e a s b u...

Страница 13: ...or rust with no flame present If so turn off heater and let cool Either remove blockage or replace burner Blocked burner flame holes will create soot TROUBLESHOOTING Note All troubleshooting items ar...

Страница 14: ...see Cleaning and Maintenance page 12 or replace burner orifice 2 Contact local propane LP gas company 3 Replace burner orifice 4 Reconnect leads see wiring diagram Delayed ignition burner 1 Manifold...

Страница 15: ...Gas Pressure In of water Maximum 14 10 5 Minimum 11 5 Dimensions Inches H W D Heater 36 1 4 45 1 2 12 3 16 36 1 4 45 1 2 12 3 16 Carton 42 48 9 16 13 7 16 42 48 9 16 13 7 16 Weight lbs Stove 101 101...

Страница 16: ...ARTS NOT UNDER WARRANTY Contact authorized dealers of this product If they can t supply original replacement part s call PRO COM s toll free number at 1 877 886 5989 for referral information When call...

Страница 17: ...17 ILLUSTRATED PARTS BREAKDOWN BN28TYLA W BL28TYLA W BN28TYLA C BL28TYLA C BN28TYLA O BL28TYLA O...

Страница 18: ...v l a V T A T S T 1 1 9 2 0 3 8 0 L M r o t i n g I 1 1 0 1 8 1 2 5 4 5 T I S 5 4 5 0 3 6 0 e v l a V l o r t n o C t a t s o m r e h T T I S 1 0 0 2 5 4 5 T I S 5 4 5 0 3 6 0 e v l a V l o r t n o C...

Страница 19: ...19 ILLUSTRATED PARTS BREAKDOWN BN28TYLA W BL28TYLA W BN28TYLA C BL28TYLA C BN28TYLA O BL28TYLA O...

Страница 20: ...o l o C e s a B 1 6 1 0 6 1 0 L B l e n a P t n u o M r e w o l B 1 1 1 7 1 0 5 0 0 L S t e k c a r B r e w o l B 2 2 2 8 1 0 2 1 0 L B y d o B 1 1 1 9 1 0 7 0 0 L B r o o l F x o b e r i F 1 1 1 0 1...

Страница 21: ...the front angle See FIG 4 FIG 3 FIG 4 STEP 4 Insert the pinhole on the upper part on the left side of log 1 Place the lower part of log 4 on the flat roof at the left side of log 3 See FIG 5 STEP 5 I...

Страница 22: ...22 Mantel Installation Instructions...

Страница 23: ...onnectors on the left part of top base panel in the corresponding holes of left base panel see FIG b Then screw down the connectors using Philips screwdriver see FIG c 3 Piece together the right base...

Страница 24: ...ssembled structure and front base panel marked 4 Note Insert the connectors on the front base panel in the seven corresponding holes of assembled struc ture see FIG g Then screw down the connectors us...

Страница 25: ...apping screws and anchors as shown in FIG 1 assembling the anchors see page 27 Tear the dust proof plastic film off regulator Connect one end of hose metal fitting provide with fireplace to regulator...

Страница 26: ...26 Install base Push base to mantel and ensure the rear part of the base fits with the col umn face closely see FIG 3 FIG 2 FIG 3...

Страница 27: ...lls wall areas between studs or solid walls concrete or masonry a Drill holes at marked locations using 5 16 drill bit For solid walls concrete or masonry drill at least 1 deep b Fold wall anchor as s...

Отзывы: