background image

If the unit is 

not

 connected to the mains using the fused plug supplied, or a fused

connection unit, it must be protected by means of a fuse or MCB at the final

distribution board of rating not exceeding 6 A. A readily accessible local isolating

switch should be provided to allow the unit to be disconnected from the supply

when necessary.

Any fixed wiring installed to supply power to this starBOX should comply with

BS 7671  (IEE  wiring  regulations)  and,  where  relevant,  Part  P  of  the  building

regulations. StarBOXes are of Class 2 construction and do not require a protective

earth connection. This does not obviate the need to provide a circuit protective

(earth) conductor in the supply wiring, as required by BS 7671.

System equipotential bonding

Distribution systems supplying signals to more than one household should comply

with the safety requirements of BS EN 60728-11. This effectively requires earthed

equipotential bonding of the system. (Isolated outlet plates cannot be used with

starBOX  units  for  functional  reasons.)  Although  not  mandatory  in  single

households, the use of system earth bonding is strongly recommended for all

installations.  All  starBOXes  are  provided  with  an  earth  terminal.  A  bonding

conductor of 4 mm² should be provided, connected to the main earth terminal of

the electrical installation which supplies the unit. Bonding may be effected using

PRO

ception proBAR5 or proBAR8 equipotential bonding bars.

User’s equipment connections

Master location

Figs. 2, 3

 and 

4

 show typical wiring diagrams for the user’s equipment at the

master location. Some points to note are:

n

When using Sky*-only remote control from the extension rooms, the RETURN

connection to the master outlet plate must come directly from RF OUT-2 of the

Sky receiver (Fig. 2). RF OUT-1 should be connected to the local main TV. The

starBOX provides 9 V DC power for remote receiver ‘eyes’ on all extension

room outputs. Note that some Sky receivers require their RF OUT-2 power

option to be enabled in order for remote control extension to work. On the

Sky handset press SERVICES, 4, 0, 1, SELECT, then select the SECOND OUTLET

POWER SUPPLY option. Set this to be ON, SAVE SETTINGS and BACK UP out

of the menu.

n

When using the starLINK remote control system the UHF RETURN connection

must be fed from the LINE OUT connector of the proSTL1BASE base unit. The

starLINK system may be used with a wide variety of equipment, including Sky*

and Freeview

†

 receiver boxes, most VCRs, DVD players, etc. (

Figs. 3 & 4

). Full

installation instructions for the starLINK system are contained in the instructions

supplied with the proSTL1KIT product.

n

TV signals (UHF) will only be available in the extension rooms if a feed is

provided  to  the  UHF  RETURN  connection  (see  explanation  above  in  the

‘Principles’ section). If no remote control extender system is to be used, a two-

way passive splitter should be employed if necessary to split the RF output

from the final item in the UHF ‘loop-through’ chain, with one leg of the splitter

connected to the main TV and the other leg feeding UHF RETURN.

Page 4

Page 9

Fig.4 - Main viewing location wiring diagram for Freeview with starLINK remote control.

Telephone line

Master outlet plate

proOUT35RT

ANT IN

Hi-Fi

tuner

Main TV

RF OUT

ANT IN

PSU

VCR

Freeview

ANT IN

RF OUT

From starBOX

1-R

blaster

LINE OUT

TV

IN

Base unit

MASTER OUT

LNB2 OUT

UHF RETURN

Fig.5 - Extension room installation with remote control.

Note: SCART and telephone connections have been omitted from these diagrams for clarity.

352FHSWLRQ

7

9

,1

SUR6$7(<(

0N

Hi-Fi

tuner

proSAT1EYE (Sky*-only)

or

proSTL1EYE (starLINK)

TV

proOUT12C

From

starBOX

Coupler

Отзывы: