ESTABLISHING COMMUNICATION

Refer to Master Thermostat 

Technician Setup Menu to set 

High & Low limits.

NOTE:

The  Master Thermostat Tech setting for the 
discharge air sensor must be set to

 

YES. 

See 

Master Thermostat

 manual for instructions.

1.

2.

Example Step 2.

Found Discharge Air Sensor Screen

Easy, two step communication link set up.

Connection button 
located inside the 

discharge air sensor

Important:

DO NOT press the connection 

button again after Step 2 (above) 

has been completed. Holding 

the button a second time will 

break the communication link 

and the connection steps will 

have to be repeated.

DAS

While the 

Master Thermostat

 

is on the 

Discharge Air 

Sensor

 screen, and set to yes, hold down the 

connection button on the inside of the 

Sensor 

until the 

Master Thermostat 

shows the letters 

YE

 and says 

Found DAS.

Connecting to the Master Zone Thermostat

Communication Note

The discharge air sensor sends a temperature reading 

signal to the Master Thermostat every 5 minutes, or if a set 

temperature limit has been reached.

If the temperature has exceeded a set limit, the 

Master Thermostat will shut off the heat or cool 

source while leaving the fan energized.

It remains in this mode until the next temperature

reading signal. (5 Minutes)

At that time if the temperature limits are not 

exceeded, the heat or cool source will be energized

if there is still a call.

Industry ‘Average’ Limits

High limit:

   - Heat pump: 120-140* F

   - Electric/Gas Furnace: 140-160*F

 

Low Limit:

   - 45*F for most systems