Pro1 Technologies T731W Скачать руководство пользователя страница 5

15

Wireless Network Specifications

•  

The thermostat will attempt to pair with the first Basemodule it 

   “hears”.  Do not attempt to create more than one “pair” at the same

   time in the same place.

•  

To ensure paring success, place the T731W/O within a few feet of 

   the Base module while pairing. Once paired, the signal strength 

   tech menu can be used to ensure a robust wireless connection.

•  

Placing either device in or around large metal objects can severely 

   degrade the wireless range.

•  

The wireless network will automatically recover in the event of a 

   power loss or temporary signal loss.

Duration of 

Occupancy 

(Only displayed if 

Local Occupancy 

Sensor is ON) 

Tech Setup Steps 

Adjustment Options

Default

LCD Will Show

Local 

Occupancy 

Sensor 

When using the Occupancy model 

the installer can choose to utilize 

the occupancy sensor to set back 

the room temperature while it is 

not being occupied.

Set the heating temperature and 

fan operation that you would like 

the system to be while the space 

is being occupied. 

Full temperature ange defined 

by setpoint limits.

First adjust the temperature 

using the + and – buttons.  

Use the Fan button to change 

the fan operation.

Set the cooling temperature and 

fan operation that you would like 

the system to be while the space 

is being occupied. 

When the occupancy sensor is 

turned on you have the ability 

to set how long the thermostat 

will go into occupancy mode 

everytime a person is sensed.

30 = 30 minutes, 1 = 1 hour, 

2 = 2 hours, 3 = 3 hours, 4 

= 4 hours, 5 = 5 hours, 6 = 

6 hours, 7 = 7 hours, 8 =8 

hours, 9 = 9 hours, 10 = 10 

hours, 11 = 11 hours, and 12 

= 12 hours. 

8

Full temperature ange 

defined by setpoint limits.

First adjust the temperature 

using the + and – buttons.  

Use the Fan button to change 

the fan operation.  

Set the cool temperature and fan 

operation that you would like the 

system to be while the space is 

unoccupied. 

Full temperature ange defined 

by setpoint limits.

First adjust the temperature 

using the + and – buttons.  

Use the Fan button to change 

the fan operation.  normal high 

intensity all the time.

Occupancy Models Only

ON                                                      

OF(OFF)

OF

Occupied 

Cool Setting 

(Only displayed if 

Local Occupancy 

Sensor is ON) 

78˚

Occupied 

Heat Setting 

(Only displayed if 

Local Occupancy 

Sensor is ON) 

70˚

Unoccupied 

Cool Setting 

(Only displayed if 

Local Occupancy 

Sensor is ON) 

83˚

Occupancy 

Sensitivity 

Setting

(Only displayed if 

Local Occupancy 

Tech Setup Steps 

Adjustment Options

Default

LCD Will Show

Set the heat temperature and fan 

operation that you would like the 

system to be while the space is 

unoccupied. 

Set the level of sensitivity of 

the occupancy sensor. Lowering 

the sensitivity will cause the 

sensor to respond only to larger 

movements.

High Sensitivity:

This is the most sensitive 

setting and 

will detect very slight mo-

tions. This is the recommend-

ed setting because it will work 

well for nearly all applications.  

Will detect any movement.

Medium Sensitivity:

This is the medium sensitive 

setting and can be used 

without pets setting it off.

Low Sensitivity:

This is the least sensitive 

setting and can 

be used in areas of major or 

large motions.  This will not be 

set off by pets, small children, 

or people more than 20’ from 

the sensor location.  

HI

Occupancy Models Only

Full temperature ange 

defined by setpoint limits.

First adjust the temperature 

using the + and – buttons.  

Use the Fan button to 

change the fan operation.  

Unoccupied 

Heat Setting 

(Only displayed if 

Local Occupancy 

Sensor is ON) 

62˚

Technician Setup

Technician Setup

16

Specifications

0F

OCC SENSOR

8

OCC LENGTH

75

OCC COOL

70

OCC HEAT

83

UNOCC HEAT

62

UNOCC COOL

HI

19

Network Specifications

•  

A single basemodule can support up to 7 remotes.

•  

If more than one Tthermostat is connected to a base module, the 

   system will control to the last interaction

•  

Thermostat units will require up to 60 seconds to reflect changes 

   elsewhere in the network.

•  

A base module paired with another base module will work as a 

   “repeater”. It will match the relay state of the main base module.

Network Capabilities 

Specifications

The display range of temperature ... 41˚F to 95˚F (5˚C to 35˚C)

The control range of temperature.... 44˚F to 90˚F (7˚C to 32˚C)

Load rating.................................................1 amp per terminal, 1.5 amp 

                                                                      maximum all terminals combined

Swing (cycle rate or differential) ...... Heating is adjustable from 0.2˚ to 2.0˚

                                                                         Cooling is adjustable from 0.2˚ to 2.0˚

Power source ...........................................18 to 30 VAC, NEC Class II, 50/60 Hz 

                                                                      for hardwire

                                                                      Battery power from 2 AA Alkaline 

                                                                      batteries

Operating ambient ............................... 32˚F to +105˚F (0˚C to +41˚C)

Operating humidity .............................. 90% non-condensing maximum

Dimensions of thermostat ................. 4.7”W x 4.4”H x 1.1”D

Frequency ................................................ 916 MHz

Thermostat

Load rating ............................................... 1 amp per terminal, 1.5 amp 

                                                                       maximum all terminals combined.

Power source ...........................................18 to 30 VAC, NEC Class II, 50/60 Hz 

Operating ambient ............................... 32˚F to +150˚F (0˚C to +65˚C)

Operating humidity .............................. 90% non-condensing maximum

Base Module 

20

Changes or modifications not expressly approved by the manufacturer could 

void the user’s authority to operate the equipment.

Note: