When connecting the Power Cord, use the 
following items when performing wiring. 
(Items are made by Phoenix Contact.)

„

Connecting the ST Power Cord

(1) Confirm that the ST unit’s Power Cord is 

unplugged from the power supply.

(2) Strip the power cord, twist the 

conductor’s wire ends, insert them into 
the pin terminal and crimp the terminal. 
Attach the terminal to the power 
connector.

• Use a flat-blade screwdriver (Size 0.6 

X 3.5) to tighten the terminal screws.
The torque required to tighten these 
screws is 0.5 to 0.6 N

m [5-7Lb

In.].

• Do not solder the cable connection.

(3) Attach the Power connector (Plug) to the 

Power Connector.

2.

Power Supply Cautions

• Input and Output signal lines must be sepa-

rated from the power control cables for 
operational circuits.

• To improve the noise resistance, be sure to 

twist the ends of the power cord wires 
before connecting them to the Power con-
nector (Plug).

• The ST unit’s power supply cord should 

not be bundled with or kept close to main 
circuit lines (high voltage, high current), or 
input/output signal lines.

• To reduce noise, make the power cord as 

short as possible.

• If the supplied voltage exceeds the ST 

unit’s range, connect a voltage transformer.

• Between the line and the ground, be sure to 

use a low noise power supply. If there is an 
excess amount of noise, connect a noise 
reducing transformer.

• The temperature rating of field installed 

conductors: 75°C only.

• Use voltage and noise reducing trans-

formers with capacities exceeding 
Power Consumption value.

• Must be used with a Class 2 Power Supply. 

(24VDC)

• Connect a surge absorber to handle power 

surges.

• Be sure to ground the surge absorber 

(E1) separately from the ST unit (E2).
Select a surge absorber that has a 
maximum circuit voltage greater then 
that of the peak voltage of the power 
supply.

Recommended 
Driver

SZF 1-0.6x3.5 
(1204517)

Recommended 
Pin Terminals

AI 0.75-8GY (3200519)
AI 1-8RD (3200030)
AI 1.5-8BK (3200043)
AI 2.5-8BU (3200522)

Recommended 
Pin Terminal 
Crimp Tool

CRIMPFOX ZA 3 
(1201882)

Power 
Connector 
(Socket)

Power 
Connector 
(Plug)

+

-

Rear

FG

Lightening Surge Absorber

E1

E2

FG

ST

Содержание ST3200 Series

Страница 1: ...fully packed with special attention to quality However should you find anything damaged or missing please contact your local ST distributor immediately About the Manual For the detailed information on ST3000 series refer to the following manual ST3000 Series Hardware Manual Maintenance Troubleshooting ST3000 Series Hardware Manual can be selected from the help menu of GP Pro EX or downloaded from ...

Страница 2: ...lug type RS232C is supported E Serial Interface COM2 AST3201 A1 D24 has Dsub 9 pin plug type and supports RS422 RS485 1 AST3211 A1 D24 has Dsub 9 pin socket type and supports RS485 MPI only 1 RS485 is compliant with AST 3201A units with revision code C or later Revision page 11 Front A Rear E D B C Bottom LED ST Status Green lit Normal operation power is ON or OFFLINE operation Orange blinking Dur...

Страница 3: ...sulation Resistance DC500V 10MΩ min between charging and FG terminals Physical Surrounding Air Temperature 0 to 50 C 1 1 When using in an environment where the temperature becomes or exceeds 40 C for an extended period of time the screen contrast level may decrease from its original level of brightness Storage Temperature 20 to 60 C Ambient Humidity 10 to 90 RH Wet bulb temperature 39 C max no con...

Страница 4: ... isolation unit CA3 ISO232 01 on COM1 COM1 Recommended Cable Connector XM2D 0901 made by OMRON Corp Recommended Jack Screw XM2Z 0073 made by OMRON Corp Recommended Cable Cover XM2S 0913 made by OMRON Corp Interfit Bracket 4 40 inch screws are used Pin RS232C Signal Name Meaning 1 CD Carrier Detect 2 RD RXD Receive Data 3 SD TXD Send Data 4 ER DTR Data Terminal Ready 5 SG Signal Ground 6 DR DSR Dat...

Страница 5: ...ame Meaning 1 RDA Receive Data A NC 2 RDB Receive Data B NC 3 SDA Send Data A LINE Line 4 ERA Data Terminal Ready A RS RTS Request to Send 5 SG Signal Ground SG Signal Ground 2 2 In COM2 on the AST3211 A1 D24 the SG and FG terminals are isolated 6 CSB Clear to Send B 5V 5V External Output 3 4 3 The 5V output for Pin 6 is not protected against overcurrent To prevent damage or unit malfunctions use ...

Страница 6: ...lation 1 Create a Panel Cut following the dimen sions in the table below 2 Confirm that the installation gasket is attached to the ST unit and then place the ST unit into the Panel from the front It is strongly recommended that you use the installation gasket since it absorbs vibration in addition to repel ling water For the procedure for replacing the installation gasket refer to ST3000 Series Ha...

Страница 7: ...nected be sure the wire is grounded 1 Wiring the DC type power supply cable Power Cord Specifications Use copper conductors only Power Connector Plug Specifications The power connector plug is CA5 DCCNM 01 made by Pro face or MSTB2 5 3 ST 5 08 made by Phoenix Contact Insertion Slot Recess Hook the fastener on the Recess Panel Installation Fastener ST Hook and secure the fastener on the panel with ...

Страница 8: ...bundled with or kept close to main circuit lines high voltage high current or input output signal lines To reduce noise make the power cord as short as possible If the supplied voltage exceeds the ST unit s range connect a voltage transformer Between the line and the ground be sure to use a low noise power supply If there is an excess amount of noise connect a noise reducing transformer The temper...

Страница 9: ...long grounding wire replace the thin wire with a thicker wire and place it in a duct 4 Input Output Signal Line Cautions All ST Input and Output signal lines must be separated from all operating circuit power cables If this is not possible use a shielded cable and ground the shield To prevent the USB cable from coming off Attaching the USB Holder 1 Before starting the procedure lift up the tab on ...

Страница 10: ... aware of the following items when building the ST into an end use product The ST unit s rear face is not approved as an enclosure When building the ST unit into an end use product be sure to use an enclosure that satisfies standards as the end use product s overall enclosure The ST unit must be used indoors only Install and operate the ST with its front panel facing outwards If the ST is mounted ...

Страница 11: ...n 8 2 52 Nanko higashi Suminoe ku Osaka 559 0031 JAPAN TEL 81 0 6 6613 3116 FAX 81 0 6 6613 5888 http www pro face com Copyright 2006 Digital Electronics Corporation All rights reserved 085886B AST3200 MT01E BTH 2007 7 SS F Inquiry Do you have any questions about difficulties with this product Please access our site anytime that you need help with a solution http www pro face com otasuke Please be...

Отзывы: