GP-37W3 Series User Manual
3-1
Chapter
3
Installation and Wiring
1. Installation
2. Wiring Cautions
3. Tool Connector
Decide the panel’s thickness based on the level of panel strength
required.
Before installing the GP into a cabinet or panel, check that the installa-
tion gasket is securely attached to the unit.
3.1
Installation
3.1.1
Installation Procedure
Creating a Panel Cut
It is strongly recommended that you use the gasket since it
absorbs vibration in addition to repelling water.
Place the GP on a level surface with the display panel facing
downward. Check that the GP’s installation gasket is seated
securely into the gasket’s groove, which runs around the
perimeter of the panel’s frame. For details about installing
the gasket, refer to
7.1.2 Installation Gasket Replacement
Create the correct sized opening required to install the GP, using the installation
dimensions given.
2.5.3 “GP Panel Cut Dimensions”
The installation gasket, installation brackets and attachment screws are all required when
installing the GP.
Installation gasket
Rear of GP
Cut Out
Area
Panel
1.6mm(0.06in.) to 5mm (0.2in.)
•
Check that the installation panel or cabinet’s surface is flat, in good condition
and has no jagged edges.
•
Panel thickness should be from 1.6mm (0.06in.) to 5mm (0.2in.).