4.5 Cable Diagram at the time of replacement
The connection cable for GP-3300 series can be used for GP-4301T/TW.
But please note that
there are precautions and restrictions as described below when
replacing
GP-3300T/S/L and GP-3301S/L
.
・
When a RS-422/485 device is connected via the COM1 port,
if GP-3300T/S/L or
GP-3301S/L is replaced with GP-4301T/TW, it will be connected via the
COM2 port of GP-4301T/TW.
(The cable diagram can be still used.)
Before GP-4301T/TW is connected, be sure to change the port setting to COM2 on
the Device/PLC setting. Also, please check the communication settings with
GP-Pro EX Device/PLC Connection Manual just in case.
(
http://www.pro-face.com/otasuke/files/manual/gpproex/new/device/index.htm
)