FP2600-T11 User Manual
3-5
Installation and Wiring
•
When connecting the FG terminal, be sure to connect the ground wire.
Not grounding the FP unit will create excessive noise and vibration.
•
Wherever possible, use thick wires (max. 2mm
2
) for power terminals,
and provide an extra twist to the wire before connecting it.
•
The ring terminal size should be as follows.
• To avoid a power short when loosening power terminal screws, use a power
terminal with plastic sleeves.
3-2 Wiring
3-2-1 Power Cable Connection
• To prevent electrical shocks, be sure the Power Cable is plugged first into
the FP unit, then into the wall (main supply).
• Your FP2600-T11 uses input voltage of only AC100V. If your power supply
is greater than that required by your unit, it may damage both the power source
and the FP unit.
• In lieu of the power switch on the FP unit, please connect a breaker unit.
Warning
3.2 mm
less than 6.0 mm
FG
Power Terminal Block
FG *1
Crimp-on Ring
Terminals
N
L
N
L
100V Unit
FP2600-T11
FP2600-T11
(Rear)
*1
The three power terminals are:
AC100V L = AC Input Terminal—live line
AC100V N = AC Input Terminal—neutral line
FG
= Ground Terminal connected to the FP chassis
Содержание FP2600-T11