TROUBLESHOOTING      

 

    

PROBLEM: No LED indicators illuminated on battery status indicator. 

    

 

    

Solution Sequence:     
1. Confirm that current is being delivered to the charger. Use a meter or test light to check the AC power supply from its source 

through all connecting points up to the charger.     

2. Check that the AC circuit breaker (on front of the unit) is depressed.     
3. Call technical support for further assistance (800.742.2740).     

 

    

PROBLEM: The charge status indicator changes rapidly back and forth from red to green or the green LED will not 

illuminate after excessive charging time (24 hours or more). 

    

     

Solution Sequence:     
1. Disconnect AC power from the charging system. This indication may signify a possible battery problem.     
2. Call technical support for further assistance (800.742.2740).     

PROBLEM: A green LED was illuminated before disconnecting the power from the charger, but upon reconnection, 

red LEDs appear and remain on.

     

     

This is the normal operating procedure for the system. It indicates that a reanalysis of the battery status was initiated and after a 

series of steps the green LED will illuminate.     

 

    

LIGHT EMITTING DIODES (LED) FAULT CODE INDICATIONS      

The microprocessor is constantly monitoring the charger circuitry and will both detect and display blinking LED indications if a 

fault is detected.  The battery type LED will be 

OFF

 during a fault code condition.       

 

30 & 60% RED LEDS BLINKING ………………..…..…FORMING STAGE TIMEOUT SHUTDOWN  

    

This indication occurs if the battery voltage has not risen above 1.75 volts per cell within the first 3 hours of charging.   This indicates that a possible battery 

problem exists and that the charge cycle has been terminated at this point.   

   

 

    

30, 60 & 90% RED LEDS BLINKING............................................OVERALL TIMER SHUTDOWN  

    

This  indication  occurs  if the charger  has  not completed the charge cycle  within  the  allowable factory set  time  period.   This  indicates  that  a  possible  battery 

problem exists and that the charge cycle has been terminated at this point. 

    

 

    

30 & 90% RED LEDS BLINKING …..…..............................INTERNAL OVERTEMP SHUTDOWN  

    

This indication occurs if the charger circuitry has detected operating temperatures inside the charger enclosure that are above factory specified levels.  This 

could indicate that a possible charger problem exists and that the charge cycle has been terminated.   

    

 

    

30% RED & 100% GREEN LEDS BLINKING …..….......................... BULK DV/DT STAGE SHUTDOWN  

    

This indication occurs if the battery voltage does not rise properly during the Bulk Stage. This indicates that a possible battery problem exists and that the charge 

cycle has been terminated at this point.  Please call technical support for further assistance (800.742.2740). 

 

30% RED & 100% GREEN LEDS ALTERNATE BLINKING ON OFF…..….................. NO BATTERY DETECTED  

    

This will be the NORMAL indication when the charger is plugged into A/C but not connected to a battery pack.  Please call technical support for further assistance 

(800.742.2740). 

    

 

Note: Disconnecting and reconnecting the AC power supply cord will reset the charger. 

    

 

 

 

 

 

 

 

Содержание i36154815

Страница 1: ...ns before installing or applying AC power to your Pro Charging Systems PCS charger Contact technical support at PCS with any product installation or service questions 800 742 2740 Pro Charging Systems...

Страница 2: ...esult in minor personal injury product or property damage This symbol means BE ALERT Your safety or the safety of others is involved PERSONAL SAFETY PRECAUTIONS Always read all instructions before usi...

Страница 3: ...ceived a sharp blow been dropped or otherwise damaged in any way have it repaired by an authorized technician Do not disassemble charger contact PCS technical support when service or repair is require...

Страница 4: ...le chargeur dans un espace close et ou ne pas gener la ventilation Clean battery terminals Be careful to keep corrosion from coming into contact with eyes Add distilled water to each cell until batte...

Страница 5: ...charge will be displayed by illumination of the Light Emitting Diodes LEDS on the battery status indicator located on the front of the unit DO NOT connect or disconnect the DC output electrical cord t...

Страница 6: ...a 100 indication If this occurs reset the AC connection and allow the charger to identify a 48V system and completely charge the battery pack CHARGING INDICATIONS When your battery charging system is...

Страница 7: ...60 RED LEDS BLINKING FORMING STAGE TIMEOUT SHUTDOWN This indication occurs if the battery voltage has not risen above 1 75 volts per cell within the first 3 hours of charging This indicates that a po...

Страница 8: ...Chargers that are purchased more than two years beyond the date of production will automatically have a warranty start date that will be the two year anniversary of the production date This limited wa...

Отзывы: