background image

Page 4 

Air Handling and Fan Coil Units Subzoned with
Therma-Fuser VAV diffusers, Form 6.7.

DX Equipment Zoned with Therma-Fuser VAV
diffusers, Form 6.5.

SUPPLY AIR TEMPERATURE 

The sources of cooling and heating are controlled from 
supply air temperature. As with all VAV systems, the 
goals are to achieve a constant supply air temperature 
(may be reset to another constant supply air 
temperature) and to limit the supply air temperature. 
Limits for supply air temperature should be between 
50°F/10°C and 68°F/20°C when cooling and between 
80°F/26.5°C and 120°F/49°C when heating. The 
heating temperature limit should be as low as possible. 
These objectives are best achieved by modulating 
chilled water valves, hot water valves and other 
variable equipment from supply air temperature. On/off 
equipment such as DX compressors and electric heat 
are cycled from supply air temperature. Use a 
discharge air sensor for the supply air temperature 
signal. 

Mode change between heating, recirculation and 
cooling is controlled from room temperature. Signals 
from one or more room temperature sensors may be 
used for mode change. When using more than one 
sensor, either a “majority rules” or a “cooling dominant” 
approach is recommended. 

STATIC PRESSURE 

As with all VAV systems, the fan must run continuously 
during occupied times. Goals of static pressure control 
are to provide enough static pressure to obtain the 
required air volume especially at the diffuser farthest 
from the fan, to avoid diffuser noise by limiting static 
pressure at both full flow and turndown and to provide 
pressure independence or consistent operation as the 
system flow changes. 

These objectives can be achieved with the usual 
methods of automatic static pressure control: bypass 
dampers, discharge dampers, zone dampers, and fan 
control (variable speed drives, inlet dampers, etc.). 
Locate the static pressure sensor as far down the duct 
as possible—at least 2/3 down the duct from the first 
takeoff. 

TROUBLESHOOTING 

Trouble shooting Therma-Fuser diffusers requires 
looking at the system as a whole. Before examining the 
Therma-Fuser diffuser for failure, it is worth the time to 
be sure the system is functioning properly and that 
something has not been over-looked. Before calling 
Acutherm, please complete the data log for all Therma-
Fuser diffusers to be evaluated. 

SYSTEM CHECK 

The system should be: 

1.

Delivering 50° - 68°F / 10° - 20°C supply air wh en
in the cooling mode.

2.

Delivering 80° - 120°F / 26.5° - 49°C supply air
when in the heating mode.

3.

Maintaining static pressure at the inlet to each
Therma-Fuser diffuser between .05 and .25"wg / 12
Pa and 62 Pa.

4.

Maintaining continuous fan operation during
occupied hours.

DIFFUSER CHECK LIST 

Once the above checks have been completed, examine 
and record the following (Conditions may vary over 
time; several measurements at different times may be 
required): 

1.

Room temperature 4ft / 1.2m above the floor
directly under the Therma-Fuser diffuser.

2.

Supply air temperature at the inlet of the Therma-
Fuser diffuser.

3.

Static pressure at the inlet of the Therma-Fuser
diffuser.

4.

Damper disc opening from the edge of the disc,
measured vertically to the housing. See Fig. 7.

Отзывы: