THERMA-FUSER™ 

THERMALLY POWERED VAV DIFFUSER 

INSTALLATION, OPERATION & MAINTENANCE 

VARIABLE AIR VOLUME SYSTEMS OPTIMIZED 

Continued on next page 

Copyright © Acutherm 2009 

Models:  STR-C    VAV cooling only

STR-HC  VAV cooling and VAV heating. 

(see Fig. 1 for dimensions.

TABLE OF CONTENTS 
INSTALLATION INSTRUCTIONS ........................ 1

 

OPENING THE APPEARANCE PANEL............... 2

 

SYSTEM BALANCING ......................................... 2

 

ADJUSTING MINIMUM FLOW ............................. 3

 

ADJUSTING TEMPERATURE SETPOINTS ........ 3

 

MAINTENANCE .................................................... 3

 

CONTROLLING THE SYSTEM ............................ 3

 

TROUBLESHOOTING .......................................... 4

 

10 YEAR WARRANTY.......................................... 6

 

DAMAGED FREIGHT CLAIM PROCEDURE 

When the diffusers are received, inspect for damage 
which may have occurred during shipment. If damage 
is evident, it should be noted on the carrier's freight bill. 
A written request for inspection by the carrier's agent 
should be made at once. 

STORAGE

 

Cartons should always be stacked on end with the 
arrows on the cartons pointing up. Do not stack cartons 
flat on the sides. Excessive weight may cause damage 
to the diffusers. 

Do not store for prolonged times at temperatures 
exceeding 130°F/56°C. 

IDENTIFICATION 

Diffusers are factory shipped one per carton. The 
model designation is on the diffuser and on the carton. 

INSTALLATION PRECAUTIONS 

When installing diffusers, make sure construction 
debris does not enter the diffuser or duct system. 

Because the models STR-C and STR-HC control room 
temperature by sensing the room air induced up the 
center of the room, care should be taken not to disturb 
room air induction and entrainment. For example, 
location next to walls or dropped lights results in the 
reflection of primary air back at the Therma-Fuser 
diffuser and should be avoided.   Either the light or the 
Therma-Fuser diffuser should be relocated. 

Fig 1. Dimensions 

OD 

Inlet 

Desig- 

nation 

Inches 

±

1

/

16

 

mm 

±3 

5

15

/

16

 

150 

7

15

/

16

 

200 

10 

9

15

/

16

 

250 

12 

11

15

/

16

 

300 

INSTALLATION INSTRUCTIONS 

1.

Inspect the carton for damage before opening.
Notify carrier if external damage exists. Submit all
claims for shipping damage to the carrier.

2.

Move diffusers (in cartons) to installation area. Note
unit identification.

3.

Remove cardboard box and cardboard insert.
Discard packing material.

4.

Attach the neck of the diffuser to the duct by
screwing through the duct into the diffuser.  A
minimum of four (4) screws is recommended.  Use
wire hangers where required by code.

Note: Air Lifter, if used, must be installed before
attaching the diffuser to the duct.

5.

Flexible duct should NOT be formed in a centerline
radius of less than 1½ times the duct diameter.

6.

Do NOT reset the temperature set point on the
STR-C and STR-HC models until the space is
occupied. The set point is factory preset for
average conditions (74°F/23°C).

7.

Balance the system. See System Balancing.

8.

After the air conditioning system is started and after
the space is occupied, where necessary adjust the
temperature set point on STR-C and STR-HC
models to suit the occupant. See Adjusting
Temperature
.