66
External Modulating Control
Factory TriMax Setting
HEATING SETTING
FACTORY DEFAULT
EZ SETUP RESET INSTALLER RESET
Heating Operation
Enabled
Demand
Switch & Outdoor Reset
Absolute Max CH Setpoint
188°F [87°C]
CH1 Maximum Setpoint
180°F [82°C]
CH1 Minimum Setpoint
120°F [49°C]
Reset Curve Coldest Day
0°F [-18°C]
Reset Curve Warmest Day
64°F [18°C]
CH2 Circuit
Enabled
CH2 Maximum Setpoint
140°F 60°C]
CH2 Minimum Setpoint
80°F [27°C]
Warm Weather Shutdown
OFF
Pump Constant Circulation
Disabled
CH Post Pump Time
1 minute
Freeze Protection
Enabled
Frost Protection Setpoint
-22°F [-30°C]
Parallel Shift Value
0°F [0°C]
CH Call Blocking
1 minute
System Pump
CH1/CH2
DOMESTIC SETTING
FACTORY DEFAULT EZ SETUP RESET INSTALLER RESET
DHW Operation
Enabled
Demand
Switch
Boiler DHW Setpoint
186°F [86°C]
DHW Storage Setpoint
140°F [60°C]
DHW On Differential
6°F [3°C]
DHW Storage Adder
46°F [25°C]
DHW Post Pump Time
1 minute
DHW Priority Timeout
OFF
DHW Priority
Enabled
DHW Call Blocking
0 minute
DHW to CH Call Blocking
1 minute
Antilegionella Function
Disabled
BOILER SETTING
FACTORY DEFAULT EZ SETUP RESET INSTALLER RESET
Prestige Model
Solo
Lockout Temperature
210°F [99°C]
Modbus Address
0=BCST
Содержание Prestige Solo 175