Prestex P404 Скачать руководство пользователя страница 3

FITTING

Before installation, the system operating 
conditions of inlet pressures, hot water 
temperature and hot and cold water flow rates 
should be determined and confirmed to be 
within the expected conditions of normal use 
shown in the table below.

Valves must operate in either a high pressure 
setting or a low pressure setting. These valves 
are not capable of operation with, for instance 
hot water supply in one pressure range and 
cold water supply in the other pressure range. 
In these conditions it is necessary to either 
boost one pressure or reduce the other so that 
both supplies are within a common pressure 
range. If your water supply cannot meet 
these conditions then the valve cannot be 
guaranteed to operate as a Type 2 valve.

Operating pressures above 5.0 Bar will require 
the installation of a pressure reducing valve.
Correct location of the mixing valve is 
important to ensure that it is accessible for 
commissioning and servicing.

•  The valve must be installed with isolation  

  valves on both the hot and cold water  
  systems as close as possible to the valve; so  
  as to allow the valve to be commissioned  
  and tested correctly.

•  The valve is supplied with integral strainers  

  on the hot and cold water supplies therefore  
  inline strainers should not be required.

•  The valve is fitted with integral “listed” non- 

  return valve cartridges which command the  
  water supply, therefore the thermostatic  
  valve is protected against cross-flow due to  
  unbalanced line pressures as required by 
  the Water Supply (Water Fittings)    
  Regulations 1999.

Assembly Procedure

•  Unpack the main valve assembly, remove the  

  three plastic protection caps and check that  
  the bores are free of debris and the end
  sealing faces are clean.

•  Unpack the two tailpieces and confirm  

  they are complete with union nuts and  
  compression nuts and olives.

•  Locate the sealing gaskets, insert them into  

  the union nuts against the faces of the
  tailpieces and screw the union nuts onto the  
  valve until a tight seal has been made.

•  Remove the compression nuts and olives  

  from the tailpieces. Locate the inlet filter
  screens and insert them into the bore of the  
  tailpieces up to the shoulder.

•  Assemble the valve to the pipework and  

  ensure the hot and cold water pipes have  
  full penetration into the tailpiece.

•  Tighten the compression nuts ensuring that  

  the end of the pipe remains in contact with
  the filter element.

The highest flow rates will be achieved under balanced pressure conditions, but the pressure at 
the valve inlets must be within a ratio of 5:1 under flow conditions and the size and layout of 
pipework and fittings must take this into account. 
 

FITTING 
 

Before installation, the system operating conditions of inlet pressures, hot water temperature and 
hot and cold water flow rates should be determined and confirmed to be within the expected 
conditions of normal use shown in the table below. 
 

 

BS1287 

BSEN1111 

Maximum static pressure (bar) 

10.0 

10.0 

Supply pressure hot and cold (bar) 

0.1 – 1.0 

1.0 – 5.0 

Hot supply °C 

55 - 65 

55 – 65 

Cold supply °C 

Maximum 25 

Maximum 25 

Mixed water temperature 

Maximum 46 

Maximum 46 

 
 
Valves must operate in either a high pressure setting or a low pressure setting. These valves are 
not capable of operation with, for instance hot water supply in one pressure range and cold 
water supply in the other pressure range. In these conditions it is necessary to either boost one 
pressure or reduce the other so that both supplies are within a common pressure range. 

If your water supply cannot meet these conditions then the valve cannot be guaranteed to 
operate as a Type 2 valve.

 

 

Operating pressures above 5.0 Bar will require the installation of a pressure reducing valve.

 

Correct location of the mixing valve is important to ensure that it is accessible for commissioning 
and servicing. 

 

 

 

 

 

 

 

                 

 

 

 

The use of sealing compounds must be avoided since they may intrude into the water   
supply and impair the valve performance. 

 

 

The valve must be so installed that it is readily accessible for commissioning and 
maintenance when being installed in accordance with TMV2. 

 

 

The valve must be installed with isolation valves on both the hot and cold water systems as 
close as possible to the valve; so as to allow the valve to be commissioned and tested 
correctly. 

 

 

The valve is supplied with integral strainers on the hot and cold water supplies therefore in-
line strainers should not be required. 

 

 

The valve is fitted with integral “listed” non-return valve cartridges which command the water 
supply, therefore the thermostatic valve is protected against cross-flow due to unbalanced 
line pressures as required by the Water Supply (Water Fittings) Regulations 1999. 

 

 
 
 
Assembly Procedure 

 

The valve body is clearly marked with ‘C’ for Cold and a blue 
indicator and ‘H’ for Hot  and a red indicator. 
The valve must be correctly connected to the respective supplies
 

•  The valve body is  

  clearly marked with  
 

‘C’

 for 

Cold

 and a  

  blue indicator and 

‘H’

  

  for 

Hot

 and a red  

  indicator.

The valve must be correctly connected   
to the respective supplies

•  The use of sealing compounds must be  

  avoided since they may intrude into 
  the water supply and impair the valve  
  performance.

•  The valve must be so installed that it is  

  readily accessible for commissioning and
  maintenance when being installed in  
  accordance with TMV2.

TMV3 Model P404.indd   3

13/2/09   15:02:46

Содержание P404

Страница 1: ... TMV2 Model P404 It is important that these guidance notes are read and fully understood prior to product installation Installation Instructions and User Guide 15mm 22MM In Line Thermostatic Mixing Valve TMV2 Model P404 2 Year BSEN 1287 BSEN 1111 TMV3 Model P404 indd 1 13 2 09 15 02 45 ...

Страница 2: ...atory WRc NSF and is a Water Regulations Advisory Scheme WRAS approved product and listed in the Water Fittings and Materials Directory IMPORTANT INTRODUCTION NOTES The valves covered by these instructions have been tested and certified as being in compliance with BS EN 1111 1999 and BS EN 1287 1999 Valves operating outside the requirements of these standards are not covered by the TMV2 Scheme and...

Страница 3: ...e and layout of pipework and fittings must take this into account FITTING Before installation the system operating conditions of inlet pressures hot water temperature and hot and cold water flow rates should be determined and confirmed to be within the expected conditions of normal use shown in the table below BS1287 BSEN1111 Maximum static pressure bar 10 0 10 0 Supply pressure hot and cold bar 0...

Страница 4: ... nuts onto the valve until a tight seal has been made Remove the compression nuts and olives from the tailpieces Locate the inlet filter screens and insert them into the bore of the tailpieces up to the shoulder Assemble the valve to the pipework and ensure the hot and cold water pipes have full penetration into the tailpiece Tighten the compression nuts ensuring that the end of the pipe remains i...

Страница 5: ...overshoots this temperature return the valve to the full cold condition and reset it to the correct temperature 0 2 C Do not set a valve on a lowered temperature as this will not provide consistent operation When the valve is set to the required temperature for the application carry out 5 cold water isolation tests to further exercise the valve Set the mixed water temperature to the required value...

Страница 6: ...ould preferably be the same as that used at installation Note If there is a residual flow during the commissioning or the annual verification cold water supply isolation test then this is acceptable providing the temperature of the water seeping from the valve is no more than 2 C above the designated maximum mixed water outlet temperature setting of the valve Any higher temperatures should occur o...

Страница 7: ...ly SPARES In order to ensure that the Prestex Model P404 thermostatic mixing valve continues to provide satisfactory service only GENUINE Pegler spare parts must be used Spare part order code Description 1 854453 Protective cap complete with screw 2 854447 Hexagon key 3 854454 Service kit 4 854449 15mm 854450 22mm Tailpiece Strainer kit 5 854451 15mm 854452 22mm Angle valve strainer kit 6 854456 1...

Страница 8: ...vailable from Pegler Yorkshire LUXURY TAP SOLUTIONS Pegler Limited St Catherine s Avenue Doncaster South Yorkshire DN4 8DF England Registered Company No 01194543 Place of Registration England Yorkshire Limited Haigh Park Road Stourton Leeds West Yorkshire LS10 1RT England Registered Company No 00401507 Place of Registration England All brand names and logo styles are registered trademarks Maintain...

Отзывы: