Operation Manual for PT-1000 & PT-2000
PARAMETERS
DEFAULT
0.5
2.0
2500
1800
0: PSI
0: NOT
INSTALLED
120
N/A
NUMBER
101
102
103
104
105
106
107
108
NAME
PUMP ON DELAY
VALVE CLOSE DELAY
HIGH PRESSURE MAX
CONTINUOUS RUN
TURN OFF TIMER
PRESSURE UNITS
OIL COOLER OPTION
FAN OFF DELAY
EMPTY
DESCRIPTION
THE VALUE ENTERED (SECONDS) IS THE
TIME THAT THE PUMP WILL DELAY TURNING
ON AFTER THE VALVE IS TURNED ON.
THE VALUE ENTERED (SECONDS) IS THE
TIME THAT THE VALVES WILL DELAY CLOS-
ING AFTER THE PUMP IS TURNED OFF.
THE VALUE ENTERED (PSI) IS THE PRES-
SURE THAT WILL TRIP AN ALARM IF THE
PUMP OUTLET EXCEEDS THAT VALUE.
THE VALUE ENTERED (SECONDS) IS THE
AMOUNT OF TIME THAT THE UNIT WILL BE
ALLOWED TO CONTINUOUSLY RUN BEFORE
TIMING OUT AND TRIGGERING AN ALARM.
CHANGE THE UNITS THAT THE PRESSURES
WILL DISPLAY ON THE HMI.
ENABLE THE FUNCTIONALITY/ALARMING
OF THE OIL COOLING UNIT
THE VALUE ENTERED (SECONDS) IS THE
TIME THAT THE COOLING FAN WILL RUN
AFTER THE PUMP IS TURNED OFF
RESERVED FOR FUTURE USE
RANGE
0.0 - 10.0
0.0 - 10.0
0 - 9999
0 - 9999
1: BAR
1: INSTALLED
0.0 - 30
N/A