Maintenance Service and Trouble Shooting   

 

The cause of sudden stop of a compressor during its running is mostly 

 

that the gas suction pressure and/or discharge pressure exceed their 

 

respective prescribed ranges, thus making a pressure-operated protective 

 

relay shut off the power to the compressor and stop it. In the following we 

 

discuss mainly the reasons for causing excessively high gas discharge 

 

pressure and low suction pressure. 

 

1)    Stoppage due to excessively high gas discharge pressure 

 

A)    Too much refrigerant charged into the system 

 

Analysis of Trouble 

 

The phenomenon, such as loose frosting and poor refrigerating effect, 

 

may occur if excessive refrigerant has been charged into the system. 

 

Superfluous refrigerant will occupy a certain space of the evaporator, thus 

 

reduce its heat dissipating area, and the phenomenon of "liquid striking" 

 

may occur, too. Meanwhile, dew or frost condensation may occur on the 

 

gas return tube, and the gas discharge pressure will obviously rise, when it 

 

reaches the threshold value, the protective relay will actuate and shut off 

 

the power supply to the compressor. 

 

Remedy 

 

Open the tubing, re-evacuate and then charge the system with a proper 

 

quantity of refrigerant. 

 

b)    Air left in the system 

 

Analysis of Trouble 

 

The residual air in the system will circulate together with the refrigerant 

 

in the system. The major symptoms caused by this residual air is higher 

 

gas discharge pressure, higher discharged gas temperature (the gas 

 

discharge tubing is considerably hot when you feel it with your hand), and 

 

poorer refrigerating effect. Furthermore, the gas discharge pressure will 

 

exceed its normal value when the compressor has run for a period not too 

 

long, thus making the protective relay actuate and bring to a stoppage. 

 

Remedy 

 

Check up how the air has been left in the refrigerating system. 

 

Generally, there are two possibilities: one is that the air has been sucked 

 

into the system when repairing due to carelessness, or it has not been 

 

purged out totally when evacuating the system; the other is that there are 

 

leak points at the low pressure end of the refrigerating system. Leak points 

 

appear mostly in those low temperature parts or assemblies, because the 

 

evaporation temperature is lower for such low temperature devices, 

 

especially at the low pressure end, it is easier for the air goes into the 

 

system. Once it has been ascertained that air does exist in the system, you 

 

have to open the tubing, re-evacuate it and then charge it with refrigerant. 

 

2)    Stoppage due to electric troubles 

 

a)    Thermostat is out of control 

 

Analysis of Trouble 

 

In case the thermostat does not work in its good order or its 

 

 

20 

 

Содержание HC-698WEN

Страница 1: ...Refrigerator Service Manual Models HC 698WEN Features Energy efficiency Micro foam technology Low noise operation Thick insulation for energy efficiency Latest No 2 micro biological technology 0...

Страница 2: ...CONTENT 1 Content 1 2 Specifications 3 3 Function Schedule 4 4 System Flow Chart 5 5 Circuit Diagram 6 6 Maintenance Service and Trouble Shooting 7 7 Exploded View 26 8 List of Parts 27 1...

Страница 3: ...y Comsumption kwh 24h 1 22kW h 24h Energy Efficiency Class A Total Gross Volume L 550L Gross Freezer Volume L 204L Total Storage Volume L 537L Freezer Storage Volume L 192L Refrigerator Storage Volume...

Страница 4: ...Function Schedule Energy efficiency Micro foam technology Low noise operation Thick insulation for energy efficiency Electronic control Vocation mode function Quick freeze mode function Quick cooling...

Страница 5: ...System Flow Chart System Flow Chart 1 Schematic diagram of System Flow Chart 2 Brief Description of System Flow Chart Flows in the sequence 1 2 3 4 5 1 5...

Страница 6: ...Circuit Diagram Circuit Diagram 1 Schematic Circuit Diagram 6...

Страница 7: ...power NO Check and repair according to the section of the compessor doesn t work YES If compressor can run naturally and temperature raising of condenser is very low YES NO Refrigerant leak check and...

Страница 8: ...capacity insufficient NO Check and repair according to the section of Cooling capacity is insuffcient YES 1 The thermostat was set at the coldest position 2 The ambient temperature is very high or th...

Страница 9: ...ing 3 Cooling capacity is insufficient Cooling capacity is insufficient Is the ambient YES temperature low than 16 C Check the therostat is correct YES NO Does the refrigerant leak siowly Adjust and i...

Страница 10: ...1 Maintenance Service and Trouble Shooting 4 The compressor doesn t work The compressor doesn t work Does the refrigerated room lamp illuminate when the door is opened NO Check the power source and po...

Страница 11: ...the pressure difference is still greater after the compressor has just stopped running the refrigerant will flow for a certain time therefore this sound is a normal phenomenon 2 A click sound can oft...

Страница 12: ...efrigerator locations and natures of troubles should be determined according to their respective features therefore experience in servicing is very important to troubleshooting Service technicians wit...

Страница 13: ...d by a sound similar to water flowing this is the sound produced by the normal circulation of refrigerant within the evaporator In case only the gas flowing sound can be heard and there is no water fl...

Страница 14: ...y due to a certain trouble With this method you can reject some suspicious troubles and finally make a correct judgment 7 Analysis of Troubles and Troubleshooting A Poor Refrigerating Effect The so ca...

Страница 15: ...essive refrigerant has been charged the liquid refrigerant that cannot evaporates in the evaporator will return to the compressor and thus a phenomenon of liquid striking will occur The liquid refrige...

Страница 16: ...ator regularly if you fail to do so the frost layer on the evaporator tubing will become thicker and thicker Heat conduction will be severely affected when the whole tubing is wrapped with a transpare...

Страница 17: ...rant and seal the charging port B No Refrigerating The phenomenon that the compressor runs normally but no frost or only a little frost appears on the evaporator and the refrigerator temperature does...

Страница 18: ...t these phenomena will appear intermittently sometimes the refrigerator works well and sometimes not well In order to determine whether it is clogged with ice heat the suspicious points with hot water...

Страница 19: ...gging with dirt 3 Troubles of Compressor a Breakage of gas suction and discharge valve blocks Analysis of Trouble The compressor works by means of the opening and closing of gas suction valve and disc...

Страница 20: ...he system Analysis of Trouble The residual air in the system will circulate together with the refrigerant in the system The major symptoms caused by this residual air is higher gas discharge pressure...

Страница 21: ...er supply c Abnormal thermal protection Analysis of Trouble The compressor current is within its normal range but the thermal protector actuates repeatedly Remedy Replace the thermal protector with a...

Страница 22: ...he user for buying a stabilizer so as to step up the voltage thus normal operation can be achieved 3 Check the thermal relay to see whether its contacts are closed Analysis of Trouble The contacts of...

Страница 23: ...caused mostly by poor lubrication such ad insufficient quantity of lubricant clogging in the lubricant oil line or intermittent lubricant oil supply Dirt and other impurities in the lubricant oil will...

Страница 24: ...rated value the thermostat won t work thus the compressor runs continuously When the evaporation temperature in the system is too high the temperature sensing agent in the temperature sensor is also h...

Страница 25: ...up intensively measure the resistance between the power cord plug and the case body with an avometer the reading will be zero 0 in the worst case the fuse will be blown Check the 3 prong outlet to se...

Страница 26: ...ocations on the side surface of its case using a rubber hammer or hand hammer with a wood block in between so as to determine whether the suspended springs are out of balance or being seized H Functio...

Страница 27: ...bottle shelf MAG0 114 1 11 503602010270 R glass shelf assembly M9D9 109 4 12 501154510018 R upper drawer M9D9 116 1 13 501154510030 R bottom drawer cover M9D9 118 1 14 501154510017 R bottom drawer M9D...

Страница 28: ...rol PCB 50230101002T 1 47 501155810269 main control PCB cover MA00 1D3 1 48 502403010012 inverter signal harness MAG3 507 1 49 502905010144 top hinge assembly MA00 1B3 1 50 501155610032 left hinge cov...

Страница 29: ...4 50115371A005 F bottle shelf MAG0 105 1 76 50115561000P F door seal assembly MA00 359 1 77 50370011467H F door assembly 50370011467H 1 78 503355800013 display control PCB NAD8 502 1 79 501155810220...

Отзывы: