background image

Replacing PAC-M200-A Interface Module

Found on Split System PremiSys

®

 DOAS Units

Please read and save these instructions for future reference. Read carefully before attempting to operate or 
maintain the product described. Protect yourself and others by observing all safety information. Failure to comply 
with instructions could result in personal injury and/or property damage!

PAC-M200-A Interface Module for PremiSys

®

 Air Products

1

WARNING

Power must be shut off to the PremiSys

®

 and the M-NET power source before any work is performed.  

All electric work must be performed according to local regulation. Improper electrical work may result in 
electric shock or fire.

                         PAC-M200-A M-NET Cable Specification

Type Of cable

Shielded wire (2-conductors) 

 

CL3P/CMP, UL, RoHS

Conductor Gauge

16AWG

Cable diameter

0.189 - 0.25 inches

Remarks

Max cable length: 200 m (656 ft), Maximum length of transmission lines for centralized control and indoor/outdoor 
transmission lines (Maximum length via indoor units): 500 m (1640 ft). 

 

The maximum length of the wiring between power supply unit for transmission lines (on the transmission lines for 
centralized control) and each outdoor unit and system controller : 200 m (656 ft)

PAC-M200-A Interface Module for 

PremiSys

®

 Air Products

Premi

Sys

Premi

Sys

© 2015 Mitsubishi Electric US, Inc.

Содержание PAC-M200-A

Страница 1: ...ic work must be performed according to local regulation Improper electrical work may result in electric shock or fire PAC M200 A M NET Cable Specification Type Of cable Shielded wire 2 conductors CL3P...

Страница 2: ...LTI System and PremiSys One CITY MULTI and One PremiSys 7 One CITY MULTI and Two PremiSys 7 Two CITY MULTI and One PremiSys 7 Outdoor Reset Function 8 Control Methods 9 Memo 10 11 Back Cover 12 Figure...

Страница 3: ...e same settings as the box for replacement Refer to Outdoor Reset Function page 8 9 Replace cover on PAC M200 A P B C B TB5 TB485 SW12 SW11 SW4 SW1 SW2 SW3 3 1 3 1 3 1 S SHIELD 1 6 CN60 M NET MODBUS 1...

Страница 4: ...d according to local regulation Improper electrical work may result in electric shock or fire PAC M100 A M NET Cable Specification Type Of cable Shielded wire 2 conductors CL3P CMP UL RoHS Conductor G...

Страница 5: ...00 A 3 Disconnect the M NET wires from the TB5 terminal block 4 Unplug the Modbus wire from the CN2 connector Cut the plug off the end of the Modbus wire 5 Remove wires from box and then remove the bo...

Страница 6: ...switches are all set to 0 when shipped from the factory Use these switches to set unit addresses and branch numbers as well P B C B TB5 TB485 SW12 SW11 SW4 SW1 SW2 SW3 3 1 3 1 3 1 S SHIELD 1 6 CN60 M...

Страница 7: ...6 07 08 09 10 Two CITY MULTI Systems and one DOAS unit IDU 1 IDU 2 IDU 3 IDU 4 IDU 5 IDU 6 IDU 7 IDU 8 DOAS 1 Address 01 02 03 04 05 06 07 08 09 IDU 01 IDU 02 IDU 03 IDU 04 Address 01 Address 02 Addre...

Страница 8: ...50F 50F 45F 45F 50F 55F 60F 65F 70F Outdoor Air Reset Function Factory Setting Supply Air Setpoint Outdoor Air Temperature Higher Lower Outdoor Reset Function Use DIP Switch SW3 and SW4 to Adjust Outd...

Страница 9: ...roprocessor Supply Temp Set Point source to BMS 3 Set Microprocessor ON OFF control source to BMS 4 On central controller turn the system group to ON 5 On central controller turn the system group mode...

Страница 10: ...PAC M200 A Interface Module for PremiSys Air Products 10 Memo 2015 Mitsubishi Electric US Inc PremiSys...

Страница 11: ...PAC M200 A Interface Module for PremiSys Air Products 11 Memo 2015 Mitsubishi Electric US Inc PremiSys...

Страница 12: ...15 Mitsubishi Electric US Inc PremiSys PAC M200 A Interface Module for PremiSys Air Products PA79D251H01 June 2015 12 PremiSys is a registered trademark of Greenheck Fan Corporation Used with permissi...

Отзывы: