MAINTENANCE

This maintenance schedule is only a guideline, determined by average conditions. Actual conditions will dictate 

the frequency of cleaning and/or replacement of lamps.  Do not touch the glass portion of the lamps with bare 

hands because oils from the hands can cause “hot spots” which reduce lamp life.  Handle either by the end caps or 

use a soft cloth.  If  you accidentally touch a lamp, clean it using a soft cloth dampened with rubbing alcohol.

CLEANING THE GERMICIDAL LAMP

 

- Recommended interval: 12 months

1. Disconnect power to the unit.
2. Unplug mid-cord connectors by pressing the lock release (marked “PRESS” on the connector.)

    Remove two thumb nuts holding moisture resistant lamp socket to mounting plate and carefully remove the

    lamp socket with lamp from the mounting plate. Repeat this step for the second lamp.

3. Use a soft cloth moistened with rubbing alcohol to wipe down each lamp.  If there is a  large build-up of dust 

    particles, you may wish to use a can of air first.  Do not touch the glass portion of the lamps with bare hands.
4. Carefully slide the moisture lamp socket with lamp through the mounting plate into duct fitting over the 

    mounting studs and secure using the two thumb nuts. (Photo A)
5. Reconnect the mid-cord connector. Be sure to line up arrows on the connector. (Photo B)

    Repeat this step for the second lamp.
6. Supply power to the unit.

CLEANING THE OXIDATION UNIT LAMP

 

- Recommended interval: 12 months

1. Disconnect power to the unit.

2. Remove the two 11/32” keps nuts and remove cover. Unplug the lamp connector from the end of the lamp then 

    remove the lamp holder using a 11/32 size nut driver.  Remove the lamp by grasping the end cap and extract 

    carefully.

3. Using a soft cloth moistened with rubbing alcohol, wipe down the lamp.  If there is a  large build-up of dust 

    particles, you may wish to use a can of air first.  Do not touch the glass portion of the lamp with bare hands.

4. Slide the lamp back into the lamp opening. Reinstall lamp holder and plug the lamp connector to the end of the lamp.

5. Replace the cover and align the odor control knob with adjustment linkage by gently turning  the knob 

    until linkage clicks into place. Secure cover using the two retaining nuts.

REPLACING THE LAMPS

 

-  Recommended interval: 24 months                  

Replacement lamps are available through your HVAC contractor.  

Follow above procedure except #3 where you replace the lamps instead of cleaning them. 

(Note: standard off-the-shelf lamps are not compatible with this unit. Use of improper lamps will void warranty.)

LSKTR100-16/5   LSKTR100-12/5 

 

 

   

        UVC16HCP-RF

LAMP KITS FOR MUV7-100DR

#LSKTR100-16/5

  UVC lamp service kit with one (1) 5” 8-watt oxidation lamp and two (2) 16” 36-Watt  UV lamps.

#LSKTR100-12/5

  UVC lamp service kit with one (1) 5” 8-watt oxidation lamp and two (2) 12” 24-Watt UV lamps.

#UVC16HCP-RF

  36-Watt 16” UV lamp with built in reflector.

#UVC12HCP-RF

  24-Watt 12” UV lamp with built in reflector.

Содержание MUV7-100TR

Страница 1: ...rs d brancher avant l installation ou le service 3 Ne pas regarder la lampe directement avec les yeux Si n cessaire de le faire veuillez porter les lunettes de soleil contre les rayons U V IMPORTANT S...

Страница 2: ...or by pressing the lock release marked PRESS on the connector see photo B Remove two thumb nuts holding moisture resistant lamp socket to mounting plate and remove from the plate 2 Using the lamp moun...

Страница 3: ...replace ballast Note Standard off the shelf lamps are not compatible with this unit Use of improper lamps will void warranty WARRANTY RETURNS All electronic components carry a lifetime warranty to th...

Страница 4: ...ly power to the unit CLEANING THE OXIDATION UNIT LAMP Recommended interval 12 months 1 Disconnect power to the unit 2 Remove the two 11 32 keps nuts and remove cover Unplug the lamp connector from the...

Страница 5: ...wire to L1 white wire to L2 green wire to ground Be sure power cord is secured with included strain relief connector The unit must cycle with the furnace blower Wire unit to an EAC terminal or current...

Страница 6: ...oles with tin snips 3 Peel off the adhesive backing of the gasket on backside of mounting plate 4 Center mounting plate on hole 5 Use four self tapping screws provided to secure mounting plate on the...

Страница 7: ...clusion or limitation of incidental or consequential damages or limitation of the duration of an implied warranty so the above limitations or exclusions may not apply to the customer This Limited Warr...

Отзывы: