MAINTENANCE
This maintenance schedule is only a guideline, determined by average conditions. Actual conditions will dictate
the frequency of cleaning and/or replacement of lamps. Do not touch the glass portion of the lamps with bare
hands because oils from the hands can cause “hot spots” which reduce lamp life. Handle either by the end caps or
use a soft cloth. If you accidentally touch a lamp, clean it using a soft cloth dampened with rubbing alcohol.
CLEANING THE GERMICIDAL LAMP
- Recommended interval: 12 months
1. Disconnect power to the unit.
2. Unplug mid-cord connectors by pressing the lock release (marked “PRESS” on the connector.)
Remove two thumb nuts holding moisture resistant lamp socket to mounting plate and carefully remove the
lamp socket with lamp from the mounting plate. Repeat this step for the second lamp.
3. Use a soft cloth moistened with rubbing alcohol to wipe down each lamp. If there is a large build-up of dust
particles, you may wish to use a can of air first. Do not touch the glass portion of the lamps with bare hands.
4. Carefully slide the moisture lamp socket with lamp through the mounting plate into duct fitting over the
mounting studs and secure using the two thumb nuts. (Photo A)
5. Reconnect the mid-cord connector. Be sure to line up arrows on the connector. (Photo B)
Repeat this step for the second lamp.
6. Supply power to the unit.
CLEANING THE OXIDATION UNIT LAMP
- Recommended interval: 12 months
1. Disconnect power to the unit.
2. Remove the two 11/32” keps nuts and remove cover. Unplug the lamp connector from the end of the lamp then
remove the lamp holder using a 11/32 size nut driver. Remove the lamp by grasping the end cap and extract
carefully.
3. Using a soft cloth moistened with rubbing alcohol, wipe down the lamp. If there is a large build-up of dust
particles, you may wish to use a can of air first. Do not touch the glass portion of the lamp with bare hands.
4. Slide the lamp back into the lamp opening. Reinstall lamp holder and plug the lamp connector to the end of the lamp.
5. Replace the cover and align the odor control knob with adjustment linkage by gently turning the knob
until linkage clicks into place. Secure cover using the two retaining nuts.
REPLACING THE LAMPS
- Recommended interval: 24 months
Replacement lamps are available through your HVAC contractor.
Follow above procedure except #3 where you replace the lamps instead of cleaning them.
(Note: standard off-the-shelf lamps are not compatible with this unit. Use of improper lamps will void warranty.)
LSKTR100-16/5 LSKTR100-12/5
UVC16HCP-RF
LAMP KITS FOR MUV7-100DR
#LSKTR100-16/5
UVC lamp service kit with one (1) 5” 8-watt oxidation lamp and two (2) 16” 36-Watt UV lamps.
#LSKTR100-12/5
UVC lamp service kit with one (1) 5” 8-watt oxidation lamp and two (2) 12” 24-Watt UV lamps.
#UVC16HCP-RF
36-Watt 16” UV lamp with built in reflector.
#UVC12HCP-RF
24-Watt 12” UV lamp with built in reflector.